Home › Insights › Arc-resistant switchgear: when it's required and what an IEEE C37.20.7 rating means

Power & Distribution

# Arc-resistant switchgear: when it's required and what an IEEE C37.20.7 rating means

Entogo July 5, 2026

![Medium-voltage arc-resistant switchgear lineup in an electrical power distribution room](https://entogo.ca/_astro/arc-resistant-switchgear-ieee-c37-20-7-rating.BVaefUPy_1BVMlX.webp)

In short

Arc-resistant switchgear redirects the pressure and heat of an internal arcing fault away from anyone standing nearby, tested to IEEE C37.20.7. It is specified where crews work close to energized medium-voltage gear and calculated incident energy is high.

## Why does an internal arcing fault put operators at risk?

When a phase-to-phase or phase-to-ground fault develops inside a medium-voltage enclosure, the air in the gap ionizes and a sustained **arc** forms. Within milliseconds it heats the surrounding air to tens of thousands of degrees, vaporizes copper, and drives a pressure wave and a jet of molten metal and plasma out of the weakest opening — often a door, a viewing window, or a cable-gland plate facing a worker. Standard [metal-clad](https://entogo.ca/products/metal-clad-switchgear/) and [metal-enclosed switchgear](https://entogo.ca/products/metal-enclosed-switchgear/) is built to interrupt fault current and to segregate live parts, but its compartment barriers are not, on their own, designed to steer that blast away from a person standing at the front of the lineup.

The hazard is quantified as **incident energy**, the thermal energy a worker at a given distance would absorb, expressed in calories per square centimetre. NFPA 70E defines the **arc flash boundary** as the distance at which incident energy reaches 1.2 cal/cm², the approximate threshold for the onset of a second-degree burn on unprotected skin. On a large medium-voltage bus the incident energy at working distance can be many times that value, which is why the way an enclosure fails matters as much as whether it clears the fault.

## How does arc-resistant switchgear change the outcome?

Arc-resistant switchgear is engineered so that, during an internal arcing fault, the pressure and hot gas are contained and then vented along a controlled path — typically upward through a **plenum** or duct — instead of blowing out toward the operator. Reinforced doors, latches, and barriers hold the compartment closed while relief flaps and the exhaust channel release the energy above head height or outside the room. The design goal is not to prevent the fault but to protect anyone standing beside a closed, latched lineup while it runs.

### Accessibility types tell you which sides are protected

The performance is graded by **accessibility type**. Under the North American test guide, Type 1 construction is arc resistant at the front of the equipment only, while Type 2 is arc resistant around the entire perimeter — front, sides, and rear. A suffix such as 2B extends the rating to the condition where a control or instrument compartment door is open. The distinction is practical: a unit set against a wall with only front access may be served by Type 1, whereas a free-standing lineup that crews can walk around generally calls for Type 2.

## What does an IEEE C37.20.7 rating actually mean?

The governing reference is **IEEE C37.20.7**, the *Guide for Testing Switchgear Rated Up to 52 kV for Internal Arcing Faults*. It defines how a representative enclosure is subjected to a prospective fault current for a set duration, and how indicators mounted around the unit are used to judge whether escaping gas or flame would have injured a person. A rating is meaningful only for the tested current, duration, and accessibility type, and only when doors and covers are secured exactly as they were during the test.

Two limits are worth understanding. First, the guide applies to arcing faults occurring in air inside the enclosure with the unit properly closed; it does not cover a door left open or a fault inside a sealed component such as an instrument transformer. Second, an IEEE C37.20.7 rating is a test result for internal arcing performance — it is separate from the product safety listing and from the site **NFPA 70E** arc-flash risk assessment, which is still performed using the **IEEE 1584** incident-energy model to set boundaries and select PPE. Arc-resistant construction reduces the consequence of a fault; it does not remove the need for a study, or for rated PPE when equipment is opened or worked energized.

## Where does arc-resistant switchgear make sense?

The value is highest where people work close to high-energy medium-voltage gear and where an incident would also take critical load offline. [Data centers](https://entogo.ca/solutions/data-centers/), where operators switch live buses beside continuously loaded equipment, are a common case, as are [utility](https://entogo.ca/solutions/utilities/) substations and heavy-industry plants. Where calculated incident energy is low, or the gear is operated remotely from behind a barrier, standard construction with disciplined work practices may be sufficient. The decision should follow the arc-flash study rather than habit, because arc-resistant construction adds cost, footprint, and an exhaust-routing constraint that only pays off where the exposure is real.

## What should a buyer specify?

State the **accessibility type** (1 or 2, plus any suffix) matched to how crews will access the lineup, and the prospective fault current and clearing time the rating must cover — those figures must align with the upstream protection and the incident-energy study, since a longer clearing time raises both the arc rating needed and the calculated incident energy. Confirm the exhaust path: an internally vented lineup needs room height or a plenum route, and an indoor install needs a room that can absorb the pressure. Specify the governing documents as context — designed and built to IEEE C37.20.7, coordinated with NFPA 70E and IEEE 1584 for the site study, and installed to the applicable **NEC/CEC** rules. For the product listing, require the mark your authority having jurisdiction expects.

Entogo builds [low-voltage switchgear and motor control centers](https://entogo.ca/products/low-voltage-switchgear-mcc/) and [gas-insulated switchgear](https://entogo.ca/products/gas-insulated-switchgear/) on its own vertically integrated line, designed and built to IEEE C37.20.7; UL (cULus)/CSA certifiable on request. In-house engineering can match accessibility type, fault rating, and venting to a specific room and study, and align the switchgear with the transformers and [substations](https://entogo.ca/solutions/substations-power-distribution/) feeding it — useful when a project cannot absorb the market’s long equipment waits. For a specification review, [contact](https://entogo.ca/contact/) the engineering team.

- Switchgear
- Arc Flash Safety
- Power & Distribution
- Standards & Compliance
- Data Centers

Glossary: [Arc-resistant switchgear](https://entogo.ca/glossary/#arc-resistant-switchgear) [Metal-enclosed](https://entogo.ca/glossary/#metal-enclosed-switchgear) [Low-voltage switchgear](https://entogo.ca/glossary/#low-voltage-switchgear-ul-1558) [Gas-insulated switchgear](https://entogo.ca/glossary/#gas-insulated-switchgear)

FAQ

## Common questions

- **What is arc-resistant switchgear**: It is switchgear tested to IEEE C37.20.7 so that an internal arcing fault vents pressure and hot gas along a controlled path away from anyone standing at the equipment, rather than out the doors and covers.
- **When is arc-resistant switchgear required**: It is specified where crews work close to energized medium-voltage gear and an arc-flash study shows high incident energy, which is common in data centers, utility substations and heavy industry.
- **What is the difference between accessibility Type 1 and Type 2**: Type 1 protects the front of the equipment only. Type 2 protects the entire perimeter — front, sides and rear — so a free-standing lineup crews can walk around generally needs Type 2.
- **Does arc-resistant switchgear replace arc flash PPE**: No. It protects operators only when doors and covers are closed and latched, so workers still follow NFPA 70E and wear rated PPE when equipment is opened or worked energized.
- **Is an IEEE C37.20.7 rating the same as a UL listing**: No. IEEE C37.20.7 is a test guide for internal arcing performance, separate from a product safety listing, so confirm both the accessibility type and the listing your jurisdiction expects.

Keep reading

## Related insights

[![Public DC fast EV charging station with transmission lines and grid infrastructure behind it](https://entogo.ca/_astro/dc-fast-charging-site-transformer-switchgear-sizing.oT4SXZBz_15uHXg.webp) EV Charging ### What size transformer and switchgear does a DC fast charging site need? A DC fast charging site is sized from AC input kVA, not DC output kW, and EVSE loads carry no demand factor. Four 150 kW plus eight 350 kW dispensers draw 3,615 kVA, needing 5,000 kVA of transformer and two 3,000 A mains at 480 V. View](https://entogo.ca/insights/dc-fast-charging-site-transformer-switchgear-sizing/)[![Distribution transformer and secondary conductors feeding low-voltage distribution equipment, governed by NEC 240.21(C) tap rules and CEC Rule 26-256](https://entogo.ca/_astro/transformer-secondary-conductors-nec-240-21c-tap-rules.BX_tOclr_UXL9N.webp) Power & Distribution ### How long can transformer secondary conductors be? NEC 240.21(C) tap rules and CEC 26-256 Transformer secondary conductors get no next-size-up rule. NEC 240.21(C) allows 10 ft and 25 ft runs with ampacity floors of one-tenth and one-third of the primary device times the voltage ratio; CEC 26-256 instead demands 125% of rated secondary current at any length. View](https://entogo.ca/insights/transformer-secondary-conductors-nec-240-21c-tap-rules/)[![Three-phase distribution transformer and low-voltage switchgear at a North American facility substation](https://entogo.ca/_astro/choosing-a-facility-distribution-voltage.B10infhs_Z2obSGL.webp) Power & Distribution ### 208, 480, or 600 volts? Choosing a facility distribution voltage North American facilities are served at 120/208, 277/480, or 347/600 volts. A higher voltage moves the same power at lower current, cutting conductor size and losses while adding transformer and safety cost. Here is how to match the voltage to the load. View](https://entogo.ca/insights/choosing-a-facility-distribution-voltage/)

Project inquiry

## Turn the brief into a specified system.

[Talk to engineering](https://entogo.ca/contact/)

## Structured data (JSON-LD)

```json
{"@context":"https://schema.org","@type":"Article","headline":"Arc-resistant switchgear: when it's required and what an IEEE C37.20.7 rating means","description":"Arc-resistant switchgear redirects the pressure and heat of an internal arcing fault away from anyone standing nearby, tested to IEEE C37.20.7. It is specified where crews work close to energized medium-voltage gear and calculated incident energy is high.","image":"https://entogo.ca/_astro/arc-resistant-switchgear-ieee-c37-20-7-rating.BVaefUPy.jpg","author":{"@id":"https://entogo.ca/#organization"},"publisher":{"@id":"https://entogo.ca/#organization"},"mainEntityOfPage":"https://entogo.ca/insights/arc-resistant-switchgear-ieee-c37-20-7-rating/","inLanguage":"en","datePublished":"2026-07-05T00:00:00.000Z","dateModified":"2026-07-05T00:00:00.000Z","keywords":"Switchgear, Arc Flash Safety, Power & Distribution, Standards & Compliance, Data Centers","about":[{"@id":"https://entogo.ca/glossary/#arc-resistant-switchgear"},{"@id":"https://entogo.ca/glossary/#metal-enclosed-switchgear"},{"@id":"https://entogo.ca/glossary/#low-voltage-switchgear-ul-1558"},{"@id":"https://entogo.ca/glossary/#gas-insulated-switchgear"}]}
```

```json
{"@context":"https://schema.org","@type":"BreadcrumbList","itemListElement":[{"@type":"ListItem","position":1,"name":"Home","item":"https://entogo.ca/"},{"@type":"ListItem","position":2,"name":"Insights","item":"https://entogo.ca/insights/"},{"@type":"ListItem","position":3,"name":"Arc-resistant switchgear: when it's required and what an IEEE C37.20.7 rating means"}]}
```

```json
{"@context":"https://schema.org","@type":"FAQPage","mainEntity":[{"@type":"Question","name":"What is arc-resistant switchgear","acceptedAnswer":{"@type":"Answer","text":"It is switchgear tested to IEEE C37.20.7 so that an internal arcing fault vents pressure and hot gas along a controlled path away from anyone standing at the equipment, rather than out the doors and covers."}},{"@type":"Question","name":"When is arc-resistant switchgear required","acceptedAnswer":{"@type":"Answer","text":"It is specified where crews work close to energized medium-voltage gear and an arc-flash study shows high incident energy, which is common in data centers, utility substations and heavy industry."}},{"@type":"Question","name":"What is the difference between accessibility Type 1 and Type 2","acceptedAnswer":{"@type":"Answer","text":"Type 1 protects the front of the equipment only. Type 2 protects the entire perimeter — front, sides and rear — so a free-standing lineup crews can walk around generally needs Type 2."}},{"@type":"Question","name":"Does arc-resistant switchgear replace arc flash PPE","acceptedAnswer":{"@type":"Answer","text":"No. It protects operators only when doors and covers are closed and latched, so workers still follow NFPA 70E and wear rated PPE when equipment is opened or worked energized."}},{"@type":"Question","name":"Is an IEEE C37.20.7 rating the same as a UL listing","acceptedAnswer":{"@type":"Answer","text":"No. IEEE C37.20.7 is a test guide for internal arcing performance, separate from a product safety listing, so confirm both the accessibility type and the listing your jurisdiction expects."}}]}
```

_Markdown twin of https://entogo.ca/insights/arc-resistant-switchgear-ieee-c37-20-7-rating/ — generated at build time from the same content as the HTML page. Company facts, catalogue index and contact: https://entogo.ca/llms.txt_