Home › Insights › How to size a neutral grounding resistor (NGR): let-through current, ohms and time rating (NEC 250.36, CEC 10-302)

Power & Distribution

# How to size a neutral grounding resistor (NGR): let-through current, ohms and time rating (NEC 250.36, CEC 10-302)

Billy, Entogo November 16, 2026

![Industrial process plant power distribution where a neutral grounding resistor limits ground-fault current on a resistance-grounded 480 V or 4.16 kV system](https://entogo.ca/_astro/how-to-size-a-neutral-grounding-resistor-ngr.C9UtYybM_eYigp.webp)

Photo — Budget Bizar · [Pexels](https://www.pexels.com/photo/tall-electric-wires-by-the-cloudy-sky-in-black-and-white-25227872/) · [Pexels License](https://www.pexels.com/license/)

In short

Size a neutral grounding resistor with R = V(line-to-neutral) ÷ I(let-through), after setting the let-through current at or above the system charging current. A 480 V high-resistance system at 5 A needs 55.4 ohms continuous; a 4.16 kV low-resistance system at 400 A for 10 s needs 6.0 ohms.

## Key takeaways

- An NGR is sized from R = V(line-to-neutral) ÷ I(let-through); at 480 V a 5 A high-resistance system needs 277.1 ÷ 5 = 55.4 ohms.
- The let-through current must be at or above the system charging current 3·Ic0, or arcing ground faults can drive transient overvoltages; systems below 600 V typically run 1 to 3 A.
- NEC 250.36 permits impedance grounding from 480 V to 1 kV only with qualified maintenance, ground detectors and no line-to-neutral loads, and a neutral conductor of at least 8 AWG copper.
- In Canada a resistance-grounded system may stay energized on a first ground fault only at 5 kV or less, with no neutral loads and fault current held to 10 A or less (CEC Rule 10-302).
- A high-resistance NGR must be continuously rated; a 480 V, 5 A unit dissipates 277.1 × 5 = 1386 W for as long as the fault stays on.
- A 4.16 kV low-resistance NGR at 400 A is 6.0 ohms and absorbs about 9.6 MJ over a 10-second rating, so it is short-time rated per IEEE Std 32 duty classes.

A **neutral grounding resistor (NGR)** is three numbers on a nameplate: the **let-through current**, the **resistance** in ohms and the **time rating**. Get the current wrong and the resistor either fails to damp arcing-fault overvoltages or lets through enough current to burn the fault point. The method is short. Estimate the system **charging current**, set the let-through current at or above it, and divide the line-to-neutral voltage by that current. A 480 V high-resistance system at 5 A needs 277.1 ÷ 5 = **55.4 Ω**, continuously rated, which is 1386 W for as long as the fault stays on. A 4.16 kV low-resistance system at 400 A needs **6.0 Ω** with a 10-second rating. The scheme choice itself (solid, high-resistance, low-resistance) is covered in [choosing a power system grounding scheme](https://entogo.ca/insights/power-system-grounding-scheme-selection/). This page sizes the resistor once that choice is made, using the same transformer full-load and fault-current figures the [transformer sizing calculator](https://entogo.ca/tools/transformer-sizing-calculator/) produces.

## What does an NGR actually limit?

On a solidly grounded wye, a line-to-ground fault is a short circuit, limited only by the transformer and conductor impedance. An NGR between the transformer neutral and the grounding electrode conductor replaces that path with a known resistance. The ground-fault current then becomes a design value instead of whatever the system can deliver. Eaton’s application paper puts the solidly grounded figure for a 480 V system served by a 1500 kVA transformer at **29,200 A**. With high-resistance grounding the same fault is held to **10 A or less**, and with low-resistance grounding it is generally **200 A to 1200 A**.

Two physical limits bound the choice:

- **Floor: the charging current.** Even an ungrounded system carries a ground-fault current through the phase-to-ground capacitance of cables, motors and surge capacitors. EC&M states that the resistor current “must be greater than the system capacitive charging current to avoid transient overvoltages.” The Informational Note to **NEC 250.36(C)** says the same thing: a value “equal to or somewhat above” the charging current.
- **Ceiling: what the code lets you run on.** If the plant is to stay energized on a first fault, the current has to stay low enough to cause no appreciable damage. Canada caps it at **10 A** (below). Above that, the fault must be tripped, which makes the system **low-resistance grounded**.

## How do you estimate the charging current?

The charging current is the phasor sum of the currents returning through the two unfaulted phases’ capacitance to ground:

> 3·Ic0 = 3 × V(L-N) ÷ Xc0, with Xc0 = 1 ÷ (2π × f × C0)

where C0 is the total phase-to-ground capacitance per phase. Eaton’s 480 V example uses Xc0 = 800 Ω per phase and finds **1.04 A** (2 × 0.6 A × cos 30°); the formula above gives the same 3 × 277.1 ÷ 800 = 1.04 A. There are three ways to get the charging current. You can calculate it from the cable and equipment capacitance in the design. You can use resistor-manufacturer estimation tables. Or you can use EC&M’s screening rule of roughly **1 A per 1000 kVA** of source capacity; EC&M also gives a typical **1 A to 3 A** for systems below 600 V. EC&M also says the value should be confirmed by an actual measurement at commissioning. Between 600 V and 5 kV, charging current “can vary from 1A to 10A.” Above 5 kV it “may be greater than 25A,” which is why low-resistance grounding is almost always used there.

## Which time rating and let-through current fit each system?

The rule table below summarizes how practice and code set the current and the duty for each system class.

| System | Grounding | Typical let-through current | Time rating | What sets it |
| --- | --- | --- | --- | --- |
| 480Y/277 V, no L-N loads | High-resistance | 5 A typical, ≤ 10 A | Continuous | ≥ 3·Ic0 (NEC 250.36(C) Info Note) |
| 600 V three-wire (347/600 V wye, neutral not distributed) | High-resistance | 5 A, ≤ 10 A in Canada | Continuous | CEC Rule 10-302 ride-through limit |
| 2.4–4.16 kV, run on first fault | High-resistance | ≥ 3·Ic0, ≤ 10 A in Canada | Continuous | Charging current 1–10 A (EC&M) |
| 4.16–13.8 kV, trip on fault | Low-resistance | 200–400 A (200–1200 A range) | 10 s typical | Relay pickup and coordination |
| Charging current above 10 A | Low-resistance or split system | ≥ 3·Ic0 | Short-time | Eaton AP083005EN |
| Generator neutral | High- or hybrid | 5 A to 400 A | By duty (ride-through or trip) | EC&M generator practice |

The time ratings come from **IEEE Std 32** (now maintained as IEEE C57.32). The federal **UFGS 16311A** guide specification offers the specifier a 10-second, 1-minute, 10-minute or extended-time duty, and notes that ratings longer than 10 seconds are needed “only when the system is not taken off line by a ground fault, but merely monitored.” A high-resistance unit that carries the fault until maintenance finds it must therefore be **continuously rated**.

## Worked example: 2000 kVA, 480Y/277 V high-resistance system

A process plant takes a **2000 kVA, 13.8 kV to 480Y/277 V** pad-mounted transformer ([2000 kVA size page](https://entogo.ca/products/pad-mounted-transformer/2000-kva/)). It feeds a three-wire motor lineup and has no line-to-neutral loads, so it qualifies for high-resistance grounding under **NEC 250.36**. The design calculation gives a total phase-to-ground capacitance of **4.0 µF per phase** across cables, motors and surge capacitors.

1. **Line-to-neutral voltage.** 480 ÷ √3 = **277.1 V**. This is the voltage across the resistor during a bolted ground fault.
2. **Charging current.** Xc0 = 1 ÷ (2π × 60 × 4.0 × 10⁻⁶) = 663.1 Ω per phase; 3 × 277.1 ÷ 663.1 = **1.254 A**. Screening check: 2000 kVA × 1 A per 1000 kVA = 2.0 A, so 1.254 A is plausible.
3. **Let-through current.** It must be at least 1.254 A, and it should stay well under the 10 A ride-through ceiling. Choose the common **5 A**, which is 5 ÷ 1.254 = **3.99 ×** the charging current.
4. **Resistance.** R = 277.1 ÷ 5 = **55.4 Ω**, with insulation rated for at least the 277 V line-to-neutral voltage.
5. **Total ground-fault current.** The resistive and capacitive currents add in quadrature: √(5² + 1.254²) = √26.57 = **5.155 A**. The ground detector and the pulsing locator must be set against that figure.
6. **Continuous dissipation.** P = 277.1 × 5 = **1386 W** (equivalently 5² × 55.4 Ω). The enclosure and its location must shed about 1.4 kW indefinitely.
7. **Neutral conductor.** The ampacity must be at least 5 A, but **NEC 250.36(B)** sets a floor of 8 AWG copper or 6 AWG aluminum, so the conductor is **8 AWG copper**, fully insulated.
8. **Pulsing tap.** A pulsing contactor that shorts half the resistor drops it to 55.4 ÷ 2 = 27.7 Ω, and the fault current then alternates between 5 A and 277.1 ÷ 27.7 = **10.0 A**. That pulse is what a clamp-on ammeter follows to the faulted feeder, and it stays within a 10 A limit.

**Step 2 — system charging current 3·Ic0** — `I3 = 3 * (V / sqrt(3)) * 2 * 3.14159265 * f * C * 0.000001` with V = 480 V, f = 60 Hz, C = 4 uF → **I3 = 1.254 A**

**Step 4 — NGR resistance** — `R = V / sqrt(3) / I` with V = 480 V, I = 5 A → **R = 55.43 ohm**

**Step 5 — total ground-fault current** — `Ig = sqrt(IR ^ 2 + IC ^ 2)` with IR = 5 A, IC = 1.254 A → **Ig = 5.155 A**

**Step 6 — continuous resistor dissipation** — `P = V / sqrt(3) * I` with V = 480 V, I = 5 A → **P = 1,386 W**

> R = V(L-N) ÷ I(let-through) = V(L-L) ÷ (√3 × I)

> P = V(L-N) × I = I² × R

The transformer side of this example, 2000 kVA at 480 V, gives 2 000 000 ÷ (√3 × 480) = **2405.6 A** of secondary full-load current. That is the figure the [transformer sizing calculator](https://entogo.ca/tools/transformer-sizing-calculator/) reports and the basis for the protection rules in [sizing transformer overcurrent protection](https://entogo.ca/insights/transformer-overcurrent-protection-fault-current/). The NGR does not change the three-phase fault duty. It changes only the ground-fault duty, from thousands of amps to about 5 A.

### Results for the example

| Quantity | Value | Basis |
| --- | --- | --- |
| Line-to-neutral voltage | 277.1 V | 480 ÷ √3 |
| Charging current 3·Ic0 | 1.254 A | 4.0 µF per phase, 60 Hz |
| Let-through current | 5 A | ≥ 3·Ic0, ≤ 10 A |
| Resistance | 55.4 Ω | 277.1 ÷ 5 |
| Total ground-fault current | 5.155 A | √(5² + 1.254²) |
| Continuous dissipation | 1386 W | 277.1 × 5 |
| Pulsing current | 10.0 A | 277.1 ÷ 27.7 Ω |
| Neutral conductor | 8 AWG Cu | NEC 250.36(B) floor |
| Time rating | Continuous | Not tripped on first fault |

## Second example: 4.16 kV low-resistance system, 400 A for 10 s

A **3000 kVA, 13.8 kV to 4.16Y/2.4 kV** transformer at **5.75 %Z** ([percent impedance](https://entogo.ca/glossary/#percent-impedance)) feeds medium-voltage motors through [metal-clad switchgear](https://entogo.ca/products/metal-clad-switchgear/). Each feeder relay trips ground faults selectively, so the system is low-resistance grounded at **400 A**.

1. Full-load current: 3 000 000 ÷ (√3 × 4160) = **416.4 A**.
2. Infinite-source three-phase fault: 416.4 ÷ 0.0575 = **7241 A**.
3. Resistance: 2401.8 ÷ 400 = **6.0 Ω**.
4. Ground fault as a share of the three-phase fault: 400 ÷ 7241 = **5.5 %**, inside the 5–20 % band Eaton lists for low-resistance grounding.
5. Energy over the rating: 2401.8 × 400 × 10 s = **9607 kJ**. The resistor element is sized for that pulse, so a **10-second** rating applies, and the relay must clear well inside it.

**MV example — energy absorbed over a 10 s rating** — `E = V / sqrt(3) * I * t / 1000` with V = 4160 V, I = 400 A, t = 10 s → **E = 9,607 kJ**

## Where Canada differs

The NEC and the CEC agree on the arithmetic but not on the envelope. **NEC 250.36** (retitled “Impedance grounded systems — 480 V to 1 kV” in the 2023 edition) permits ride-through grounding with qualified persons, ground detectors and no line-to-neutral loads. It states no ampere limit; the Informational Note points to the charging current. **CEC Rule 10-302** lets a system remain energized on a ground fault only at **5 kV or less**, with **no neutral loads**, fault current controlled to **10 A or less** and a **continuously rated** grounding device. The 2006 edition carried the same 10 A / 5 kV test in Rule 10-1102(2), raised from 5 A in 2002. Since the 2018 edition, Rule 10-302 also requires protection against grounding-device failure, with detection of an **open or shorted NGR** mandatory; the 2021 edition dropped the requirement to trip immediately. A 347/600 V system that serves 347 V lighting uses its neutral, so it falls outside the ride-through test. Confirm the subrule wording against CSA C22.1:2024 and the AHJ.

**CEC case — 600 V high-resistance NGR at 5 A** — `R = V / sqrt(3) / I` with V = 600 V, I = 5 A → **R = 69.28 ohm**

## Reference: NGR ohms and watts by system voltage

R = V(L-N) ÷ I and P = V(L-N) × I. This table is the bookmark version of every example above.

| System (L-L) | V(L-N) | 1 A | 2 A | 5 A | 10 A | 200 A | 400 A |
| --- | --- | --- | --- | --- | --- | --- | --- |
| 480 V | 277.1 V | 277.1 Ω | 138.6 Ω | 55.4 Ω / 1.39 kW | 27.7 Ω / 2.77 kW | — | — |
| 600 V | 346.4 V | 346.4 Ω | 173.2 Ω | 69.3 Ω / 1.73 kW | 34.6 Ω / 3.46 kW | — | — |
| 4.16 kV | 2401.8 V | 2401.8 Ω | 1200.9 Ω | 480.4 Ω / 12.0 kW | 240.2 Ω / 24.0 kW | 12.0 Ω | 6.0 Ω |
| 13.8 kV | 7967.4 V | — | — | — | 796.7 Ω / 79.7 kW | 39.8 Ω | 19.9 Ω |

| Requirement | NEC (2023) | CEC (CSA C22.1) |
| --- | --- | --- |
| Ride-through scope | 250.36, 480 V to 1 kV | Rule 10-302, 5 kV or less |
| Ampere limit to stay energized | No ampere limit stated; ≥ charging current | 10 A or less |
| Neutral loads | Not permitted (250.36) | Not permitted for ride-through |
| Device duty | Matched to fault duration | Continuously rated for ride-through |
| Neutral-to-NGR conductor | ≥ NGR rating, ≥ 8 AWG Cu / 6 AWG Al | Sized to the device, ≥ 8 AWG (former Rule 10-1108) |
| Above 1 kV | 250.187, insulated for max neutral voltage | No ride-through above 5 kV (Rule 10-302) |
| Device failure | Ground detectors required | Open and short NGR detection (Rule 10-302) |

## What to specify

- **System charging current 3·Ic0**, from the cable and equipment capacitance study, checked against 1 A per 1000 kVA and confirmed by measurement at commissioning (**NEC 250.36** Informational Note).
- **Let-through current**, at or above 3·Ic0 and at or below 10 A where a Canadian system must ride through (**CEC Rule 10-302**), or the relay pickup for low-resistance systems.
- **Resistance and voltage rating**, R = V(L-N) ÷ I and insulation of at least the line-to-neutral voltage, from the transformer nameplate secondary voltage.
- **Time rating**: continuous for high-resistance, 10 s (or 1 min / 10 min) for low-resistance, per **IEEE Std 32** duty classes and the relay clearing time from the coordination study.
- **Neutral-to-NGR conductor**, ≥ NGR rating and ≥ 8 AWG copper (**NEC 250.36(B)**; ≥ 8 AWG under the former CEC Rule 10-1108), plus the bonding and grounding electrode conductors from the [grounding electrode conductor sizing](https://entogo.ca/insights/transformer-grounding-electrode-conductor-bonding-jumper-sizing/) method.
- **Monitoring**: ground detector, pulsing locator and open/short NGR supervision, with space and wiring provided in the [low-voltage switchgear and MCC](https://entogo.ca/products/low-voltage-switchgear-mcc/) or the transformer secondary section.

## Common mistakes

- **Choosing 1 A because “lower is safer”.** If 3·Ic0 is 1.254 A, a 1 A resistor sits below the charging current and no longer damps arcing faults. The correct minimum is ≥ 1.254 A, and 5 A is typical. The **NEC 250.36** Informational Note and a commissioning measurement catch it.
- **Using line-to-line voltage in R = V ÷ I.** 480 ÷ 5 = 96 Ω gives only 2.9 A, below the intended 5 A. The resistor sees 277.1 V, so 55.4 Ω is correct. A nameplate check of “277 V, 5 A, 55.4 Ω” catches it.
- **Specifying a 10-second resistor on a ride-through system.** A high-resistance unit carries 1386 W until maintenance clears the fault. A short-time element will overheat, so it must be continuously rated, as **CEC Rule 10-302** requires for ride-through, with the duty class named per **IEEE Std 32**.
- **Sizing the neutral conductor to the 5 A rating.** A 14 AWG conductor carries 5 A but is below the 8 AWG copper floor of **NEC 250.36(B)**. Specify 8 AWG copper, fully insulated.
- **Applying ride-through grounding to a 347/600 V lighting system.** Neutral loads disqualify it under both **NEC 250.36** and **CEC Rule 10-302**. Solid grounding applies instead, with ground-fault protection of equipment under **NEC 230.95** where a service disconnect is rated 1000 A or more on a wye system above 150 V to ground.

## Where Entogo fits

The NGR sits on the neutral of a transformer and reports to relays in the switchgear, so the three are specified together. Entogo supplies [three-phase pad-mounted transformers](https://entogo.ca/products/three-phase-pad-mounted-transformer/) designed and built to **IEEE C57.12.00 / C57.12.34**, and [metal-clad switchgear](https://entogo.ca/products/metal-clad-switchgear/) designed and built to **ANSI/IEEE C37.20.2**. It also supplies [compact secondary unit substations](https://entogo.ca/products/compact-secondary-unit-substation/) with the neutral bushing and NGR connection provisions set before shipment. All of these are UL (cULus)/CSA certifiable on request. The NGR itself is specified from the numbers above and supplied by a resistor manufacturer; the neutral bushing and the relay and monitoring interface in the switchgear are fixed at order to match it.

Start with the transformer kVA and secondary current in the [transformer sizing calculator](https://entogo.ca/tools/transformer-sizing-calculator/), carry them into the [transformer configurator](https://entogo.ca/products/transformer-quote/), and see [industrial EPC](https://entogo.ca/solutions/industrial-epc/) and [substations and power distribution](https://entogo.ca/solutions/substations-power-distribution/) for packaged plant systems. For motor lineups behind an HRG transformer, see [how to size a motor control center](https://entogo.ca/insights/how-to-size-a-motor-control-center-mcc-nec-430-24/). For the downstream short-circuit ratings, see [available fault current and SCCR](https://entogo.ca/insights/available-fault-current-sccr-what-to-specify/).

Sizing an NGR takes four numbers in order: the charging current, a let-through current above it, the resistance at line-to-neutral voltage, and a time rating that matches whether the fault is tripped or carried. At 480 V that is 1.254 A, 5 A, 55.4 Ω and continuous; at 4.16 kV it is 400 A, 6.0 Ω and 10 seconds. In Canada the ride-through current stays at 10 A or less.

Run the numbers

The rules in this article are the ones the calculator applies live. Enter your own load, voltages and code edition, then take the result into a specification.

[Open the calculator](https://entogo.ca/tools/transformer-sizing-calculator/)

## Sources

1. [EC&M, From the Ground Up (R = VL-N ÷ IR, charging current 1 to 3 A below 600 V, 10-second LRG rating)](https://www.ecmweb.com/power-quality/ground)
2. [EEPower, National Electrical Code 2023 Basics, Grounding and Bonding Part 10 (NEC 250.36)](https://eepower.com/technical-articles/national-electrical-code-2023-basics-grounding-and-bonding-part-10/)
3. [EEPower, NEC Basics, Impedance-Grounded Systems and Equipment Grounding Above 1 kV (NEC 250.187)](https://eepower.com/technical-articles/nec-basics-impedance-grounded-systems-and-equipment-grounding-above-1-kv/)
4. [IAEI Magazine, CEC 2006 Neutral Grounding Devices, Rules 10-1100 to 10-1108](https://iaeimagazine.org/2006/september2006/cec-2006-neutral-grounding-devices-rules-10-1100-to-10-1108/)
5. [Bender, Power System Design Challenges to Meet CE Code Rule 10-302](https://us-blog.bender-group.com/en-us/us-en-power-system-design-challenges-to-meet-ce-code-rule-10-302)
6. [Eaton Application Paper AP083005EN, Characteristics of different power systems neutral grounding techniques, fact and fiction](https://eatonarabia.com/wp-content/uploads/2022/01/characteristics-power-systems-neutral-grounding-techniques-fact-fiction-ap083005en.pdf)
7. [UFGS 16311A, neutral grounding resistor per IEEE Std 32 (10-second, 1-minute, 10-minute, extended-time duty)](https://ufgscriteriadocreport.tpub.com/16311A/16311A0035.htm)
8. [I-Gard, Unparalleled Protection Electrical System Grounding (quotes CEC Rule 10-302 ride-through conditions; 480 V 5 A = 55.4 ohms)](https://i-gard.com/site/assets/files/1283/ecm_final_2019.pdf)

- Switchgear
- Grounding
- NEC 250
- CEC Section 10
- Fault current
- Power & Distribution

Glossary: [Pad-mounted transformer](https://entogo.ca/glossary/#pad-mounted-transformer) [60 Hz vs. 50 Hz](https://entogo.ca/glossary/#60-hz-vs-50-hz) [Percent impedance](https://entogo.ca/glossary/#percent-impedance) [Metal-clad switchgear](https://entogo.ca/glossary/#metal-clad-switchgear) [Low-voltage switchgear](https://entogo.ca/glossary/#low-voltage-switchgear-ul-1558) [Motor control center](https://entogo.ca/glossary/#motor-control-center)

FAQ

## Common questions

- **How many ohms is a neutral grounding resistor for a 480 V system?**: Divide the line-to-neutral voltage by the let-through current. At 480 V the line-to-neutral voltage is 277.1 V, so a 5 A high-resistance unit is 55.4 ohms, a 2 A unit is 138.6 ohms and a 10 A unit is 27.7 ohms.
- **How do you choose the let-through current of a high-resistance grounding resistor?**: Set it at or somewhat above the total system charging current 3·Ic0 so the resistor damps arcing-fault overvoltages. Systems below 600 V typically run 1 to 3 A of charging current, so 5 A is the common choice; measure the charging current at commissioning.
- **What time rating does a neutral grounding resistor need?**: A high-resistance NGR that lets the plant run on a first ground fault must be continuously rated. A low-resistance NGR whose relay trips the fault is short-time rated, usually 10 seconds, with 1-minute, 10-minute and extended-time duties available under IEEE Std 32 (now IEEE C57.32).
- **What size is the conductor between the transformer neutral and the NGR?**: Under NEC 250.36 the neutral-to-impedance conductor must be fully insulated, have an ampacity at least equal to the maximum current rating of the grounding impedance and be no smaller than 8 AWG copper or 6 AWG aluminum, so a 5 A NGR still takes 8 AWG copper.
- **Can a 600 V resistance-grounded system stay energized on a ground fault in Canada?**: Yes, if the system is 5 kV or less, serves no neutral loads, limits ground-fault current to 10 A or less and uses a continuously rated grounding device. A 347/600 V system serving 347 V lighting has neutral loads, so it cannot use this ride-through.
- **How much ground-fault current does a 4.16 kV low-resistance grounded system allow?**: Low-resistance systems are commonly set between 200 and 400 A and are generally sized at 1200 A or less. At 4.16 kV the line-to-neutral voltage is 2401.8 V, so 400 A needs 6.0 ohms and 200 A needs 12.0 ohms, both short-time rated, usually 10 seconds.

Keep reading

## Related insights

[![Industrial process plant where a low-voltage motor control center feeds pumps, fans and compressors under NEC 430.24 and CEC Rule 28-108](https://entogo.ca/_astro/how-to-size-a-motor-control-center-mcc-nec-430-24.dcewEFou_1sE5H8.webp) Power & Distribution ### How to size a motor control center: feeder ampacity, NEMA starter sizes and bus rating (NEC 430.24, CEC 28-108) Size an MCC feeder at 125% of the largest motor full-load current plus the sum of the rest (NEC 430.24, CEC 28-108). A 12-motor, 522.5 hp lineup at 480 V needs 716 A, an 800 A feeder device and an 800 A bus; the same lineup at 600 V needs 573 A. View](https://entogo.ca/insights/how-to-size-a-motor-control-center-mcc-nec-430-24/)[![Commercial rooftop solar and battery energy storage sized as a microgrid to island critical loads during a utility outage](https://entogo.ca/_astro/when-does-a-commercial-microgrid-make-sense.B-97B3Ig_ZE6KsT.webp) Microgrids ### Do you need a microgrid? Islanding, resilience, and what to specify Size a microgrid island from the critical load, not the service. A 282 kW cold-store load with a 75 hp code G compressor needs a 500 kVA grid-forming inverter, a 1042 kWh battery for 4 hours and a second protection settings group, because island fault current falls from 20,918 A to about 722 A. View](https://entogo.ca/insights/when-does-a-commercial-microgrid-make-sense/)[![Dry-type transformer secondary grounding and bonding at an industrial facility, sized to NEC 250.30, Table 250.66 and CEC Rule 10-616](https://entogo.ca/_astro/transformer-grounding-electrode-conductor-bonding-jumper-sizing.BBIMY-CK_Z20qXdN.webp) Power & Distribution ### How to size the grounding electrode conductor and system bonding jumper for a transformer (NEC 250.30, CEC 10-616) Size a transformer's grounding electrode conductor from NEC Table 250.66 and its system bonding jumper from Table 250.102(C)(1), both keyed to secondary conductor area. A 150 kVA, 208Y/120 V unit on 2 x 350 kcmil needs 2/0 copper for each; above 1100 kcmil the GEC caps at 3/0 while the jumper grows at 12.5%. View](https://entogo.ca/insights/transformer-grounding-electrode-conductor-bonding-jumper-sizing/)

Project inquiry

## Turn the brief into a specified system.

[Talk to engineering](https://entogo.ca/contact/)

## Structured data (JSON-LD)

```json
{"@context":"https://schema.org","@type":"Article","headline":"How to size a neutral grounding resistor (NGR): let-through current, ohms and time rating (NEC 250.36, CEC 10-302)","description":"Size a neutral grounding resistor with R = V(line-to-neutral) ÷ I(let-through), after setting the let-through current at or above the system charging current. A 480 V high-resistance system at 5 A needs 55.4 ohms continuous; a 4.16 kV low-resistance system at 400 A for 10 s needs 6.0 ohms.","image":"https://entogo.ca/_astro/how-to-size-a-neutral-grounding-resistor-ngr.C9UtYybM.jpg","author":{"@type":"Person","@id":"https://entogo.ca/#author-billy","name":"Billy","worksFor":{"@id":"https://entogo.ca/#organization"}},"publisher":{"@id":"https://entogo.ca/#organization"},"mainEntityOfPage":"https://entogo.ca/insights/how-to-size-a-neutral-grounding-resistor-ngr/","inLanguage":"en","datePublished":"2026-11-16T00:00:00.000Z","dateModified":"2026-11-16T00:00:00.000Z","keywords":"Switchgear, Grounding, NEC 250, CEC Section 10, Fault current, Power & Distribution","abstract":"An NGR is sized from R = V(line-to-neutral) ÷ I(let-through); at 480 V a 5 A high-resistance system needs 277.1 ÷ 5 = 55.4 ohms. The let-through current must be at or above the system charging current 3·Ic0, or arcing ground faults can drive transient overvoltages; systems below 600 V typically run 1 to 3 A. NEC 250.36 permits impedance grounding from 480 V to 1 kV only with qualified maintenance, ground detectors and no line-to-neutral loads, and a neutral conductor of at least 8 AWG copper. In Canada a resistance-grounded system may stay energized on a first ground fault only at 5 kV or less, with no neutral loads and fault current held to 10 A or less (CEC Rule 10-302). A high-resistance NGR must be continuously rated; a 480 V, 5 A unit dissipates 277.1 × 5 = 1386 W for as long as the fault stays on. A 4.16 kV low-resistance NGR at 400 A is 6.0 ohms and absorbs about 9.6 MJ over a 10-second rating, so it is short-time rated per IEEE Std 32 duty classes.","citation":[{"@type":"CreativeWork","name":"EC&M, From the Ground Up (R = VL-N ÷ IR, charging current 1 to 3 A below 600 V, 10-second LRG rating)","url":"https://www.ecmweb.com/power-quality/ground"},{"@type":"CreativeWork","name":"EEPower, National Electrical Code 2023 Basics, Grounding and Bonding Part 10 (NEC 250.36)","url":"https://eepower.com/technical-articles/national-electrical-code-2023-basics-grounding-and-bonding-part-10/"},{"@type":"CreativeWork","name":"EEPower, NEC Basics, Impedance-Grounded Systems and Equipment Grounding Above 1 kV (NEC 250.187)","url":"https://eepower.com/technical-articles/nec-basics-impedance-grounded-systems-and-equipment-grounding-above-1-kv/"},{"@type":"CreativeWork","name":"IAEI Magazine, CEC 2006 Neutral Grounding Devices, Rules 10-1100 to 10-1108","url":"https://iaeimagazine.org/2006/september2006/cec-2006-neutral-grounding-devices-rules-10-1100-to-10-1108/"},{"@type":"CreativeWork","name":"Bender, Power System Design Challenges to Meet CE Code Rule 10-302","url":"https://us-blog.bender-group.com/en-us/us-en-power-system-design-challenges-to-meet-ce-code-rule-10-302"},{"@type":"CreativeWork","name":"Eaton Application Paper AP083005EN, Characteristics of different power systems neutral grounding techniques, fact and fiction","url":"https://eatonarabia.com/wp-content/uploads/2022/01/characteristics-power-systems-neutral-grounding-techniques-fact-fiction-ap083005en.pdf"},{"@type":"CreativeWork","name":"UFGS 16311A, neutral grounding resistor per IEEE Std 32 (10-second, 1-minute, 10-minute, extended-time duty)","url":"https://ufgscriteriadocreport.tpub.com/16311A/16311A0035.htm"},{"@type":"CreativeWork","name":"I-Gard, Unparalleled Protection Electrical System Grounding (quotes CEC Rule 10-302 ride-through conditions; 480 V 5 A = 55.4 ohms)","url":"https://i-gard.com/site/assets/files/1283/ecm_final_2019.pdf"}],"about":[{"@id":"https://entogo.ca/glossary/#pad-mounted-transformer"},{"@id":"https://entogo.ca/glossary/#60-hz-vs-50-hz"},{"@id":"https://entogo.ca/glossary/#percent-impedance"},{"@id":"https://entogo.ca/glossary/#metal-clad-switchgear"},{"@id":"https://entogo.ca/glossary/#low-voltage-switchgear-ul-1558"},{"@id":"https://entogo.ca/glossary/#motor-control-center"}]}
```

```json
{"@context":"https://schema.org","@type":"BreadcrumbList","itemListElement":[{"@type":"ListItem","position":1,"name":"Home","item":"https://entogo.ca/"},{"@type":"ListItem","position":2,"name":"Insights","item":"https://entogo.ca/insights/"},{"@type":"ListItem","position":3,"name":"How to size a neutral grounding resistor (NGR): let-through current, ohms and time rating (NEC 250.36, CEC 10-302)"}],"inLanguage":"en"}
```

```json
{"@context":"https://schema.org","@type":"FAQPage","mainEntity":[{"@type":"Question","name":"How many ohms is a neutral grounding resistor for a 480 V system?","acceptedAnswer":{"@type":"Answer","text":"Divide the line-to-neutral voltage by the let-through current. At 480 V the line-to-neutral voltage is 277.1 V, so a 5 A high-resistance unit is 55.4 ohms, a 2 A unit is 138.6 ohms and a 10 A unit is 27.7 ohms."}},{"@type":"Question","name":"How do you choose the let-through current of a high-resistance grounding resistor?","acceptedAnswer":{"@type":"Answer","text":"Set it at or somewhat above the total system charging current 3·Ic0 so the resistor damps arcing-fault overvoltages. Systems below 600 V typically run 1 to 3 A of charging current, so 5 A is the common choice; measure the charging current at commissioning."}},{"@type":"Question","name":"What time rating does a neutral grounding resistor need?","acceptedAnswer":{"@type":"Answer","text":"A high-resistance NGR that lets the plant run on a first ground fault must be continuously rated. A low-resistance NGR whose relay trips the fault is short-time rated, usually 10 seconds, with 1-minute, 10-minute and extended-time duties available under IEEE Std 32 (now IEEE C57.32)."}},{"@type":"Question","name":"What size is the conductor between the transformer neutral and the NGR?","acceptedAnswer":{"@type":"Answer","text":"Under NEC 250.36 the neutral-to-impedance conductor must be fully insulated, have an ampacity at least equal to the maximum current rating of the grounding impedance and be no smaller than 8 AWG copper or 6 AWG aluminum, so a 5 A NGR still takes 8 AWG copper."}},{"@type":"Question","name":"Can a 600 V resistance-grounded system stay energized on a ground fault in Canada?","acceptedAnswer":{"@type":"Answer","text":"Yes, if the system is 5 kV or less, serves no neutral loads, limits ground-fault current to 10 A or less and uses a continuously rated grounding device. A 347/600 V system serving 347 V lighting has neutral loads, so it cannot use this ride-through."}},{"@type":"Question","name":"How much ground-fault current does a 4.16 kV low-resistance grounded system allow?","acceptedAnswer":{"@type":"Answer","text":"Low-resistance systems are commonly set between 200 and 400 A and are generally sized at 1200 A or less. At 4.16 kV the line-to-neutral voltage is 2401.8 V, so 400 A needs 6.0 ohms and 200 A needs 12.0 ohms, both short-time rated, usually 10 seconds."}}],"inLanguage":"en"}
```

```json
{"@context":"https://schema.org","@type":"HowTo","name":"How to size a neutral grounding resistor (NGR): let-through current, ohms and time rating (NEC 250.36, CEC 10-302) — Worked example: 2000 kVA, 480Y/277 V high-resistance system","step":[{"@type":"HowToStep","position":1,"name":"Line-to-neutral voltage.","text":"Line-to-neutral voltage. 480 ÷ √3 = 277.1 V. This is the voltage across the resistor during a bolted ground fault."},{"@type":"HowToStep","position":2,"name":"Charging current.","text":"Charging current. Xc0 = 1 ÷ (2π × 60 × 4.0 × 10⁻⁶) = 663.1 Ω per phase; 3 × 277.1 ÷ 663.1 = 1.254 A. Screening check: 2000 kVA × 1 A per 1000 kVA = 2.0 A, so 1.254 A is plausible."},{"@type":"HowToStep","position":3,"name":"Let-through current.","text":"Let-through current. It must be at least 1.254 A, and it should stay well under the 10 A ride-through ceiling. Choose the common 5 A, which is 5 ÷ 1.254 = 3.99 × the charging current."},{"@type":"HowToStep","position":4,"name":"Resistance.","text":"Resistance. R = 277.1 ÷ 5 = 55.4 Ω, with insulation rated for at least the 277 V line-to-neutral voltage."},{"@type":"HowToStep","position":5,"name":"Total ground-fault current.","text":"Total ground-fault current. The resistive and capacitive currents add in quadrature: √(5² + 1.254²) = √26.57 = 5.155 A. The ground detector and the pulsing locator must be set against that figure."},{"@type":"HowToStep","position":6,"name":"Continuous dissipation.","text":"Continuous dissipation. P = 277.1 × 5 = 1386 W (equivalently 5² × 55.4 Ω). The enclosure and its location must shed about 1.4 kW indefinitely."},{"@type":"HowToStep","position":7,"name":"Neutral conductor.","text":"Neutral conductor. The ampacity must be at least 5 A, but NEC 250.36(B) sets a floor of 8 AWG copper or 6 AWG aluminum, so the conductor is 8 AWG copper, fully insulated."},{"@type":"HowToStep","position":8,"name":"Pulsing tap.","text":"Pulsing tap. A pulsing contactor that shorts half the resistor drops it to 55.4 ÷ 2 = 27.7 Ω, and the fault current then alternates between 5 A and 277.1 ÷ 27.7 = 10.0 A. That pulse is what a clamp-on ammeter follows to the faulted feeder, and it stays within a 10 A limit."}],"inLanguage":"en"}
```

_Markdown twin of https://entogo.ca/insights/how-to-size-a-neutral-grounding-resistor-ngr/ — generated at build time from the same content as the HTML page. Company facts, catalogue index and contact: https://entogo.ca/llms.txt_