title: "Low-Voltage Drawout Switchgear | Entogo"
description: "Low-voltage drawout (withdrawable) switchgear for ≤600 V, 60 Hz distribution, motor control and power-factor correction — up to 5000 A and 100 kAIC, with…"
url: https://entogo.ca/products/low-voltage-drawout-switchgear/
lang: en
type: website
image: https://entogo.ca/_astro/Entogo-GCS-Low-Voltage-Withdrawable-Switchgear.C5gfH0Qt.png
alternates:
  en: https://entogo.ca/products/low-voltage-drawout-switchgear/
  fr-CA: https://entogo.ca/fr/products/low-voltage-drawout-switchgear/
  es: https://entogo.ca/es/products/low-voltage-drawout-switchgear/
  ar: https://entogo.ca/ar/products/low-voltage-drawout-switchgear/
site: https://entogo.ca/
llms: https://entogo.ca/llms.txt
---

Home › Products › Switchgear & Distribution › Low-Voltage Drawout Switchgear

Switchgear & Distribution

# Low-Voltage Drawout Switchgear

≤ 600 V · up to 5000 A

![Entogo low-voltage drawout (withdrawable) switchgear](https://entogo.ca/_astro/Entogo-GCS-Low-Voltage-Withdrawable-Switchgear.C5gfH0Qt_30gep.webp)

Overview

Low-voltage drawout (withdrawable) switchgear for ≤600 V, 60 Hz distribution, motor control and power-factor correction — up to 5000 A and 100 kAIC, with drawout power circuit breakers, for data centers and industry. Designed to UL 1558/ANSI C37.20.1; UL/CSA certifiable.

Entogo designs and builds the Low-Voltage Drawout Switchgear in its own factory with a vertically integrated supply chain: this product ships in 12–18 weeks (new UL or CSA certification can extend that, within a guaranteed 36-week worst case), and every Entogo product carries a minimum 36-month manufacturer warranty.

This **low-voltage drawout (withdrawable) switchgear** handles distribution, motor control and power-factor correction on **≤ 600 V**, 60 Hz systems, with main bus ratings to **5000 A** and short-circuit withstand to **100 kAIC**. Each power circuit breaker mounts on a racking mechanism, so it can be withdrawn to test or removed for service without de-energizing the bus — the standard for data-center, power-plant and heavy-industrial systems that demand uptime.

A 30-cycle short-time withstand supports selective coordination, and NEMA 1 indoor or 3R outdoor enclosures with SCADA and metering integration suit high-automation facilities. Designed and built to **UL 1558** / **ANSI C37.20.1** with drawout breakers to **UL 1066**, and UL (cULus) / CSA certification available on request.

## Key features

- Drawout (withdrawable) low-voltage power circuit breakers for safe, fast maintenance without de-energizing the bus.
- Designed and built to UL 1558 / ANSI C37.20.1, with breakers to UL 1066, 60 Hz — UL (cULus) / CSA certification available on request.
- Distribution, motor control and power-factor correction in one switchgear line, up to 5000 A and 100 kAIC.
- 30-cycle short-time withstand for selective coordination in mission-critical systems.
- NEMA 1 indoor or 3R outdoor; SCADA / metering integration for high-automation facilities.

Custom-engineered · built to order

[Get a quote](https://entogo.ca/contact)

Lead time

12–18 weeks

Order now for estimated delivery Dec 2026 – Jan 2027.

Certification / testing may extend this per the standard and scope.

Quality & certifications

- ![UL safety certification mark](https://entogo.ca/_astro/Entogo-UL-Underwriters-Laboratories-North-America-Safety-Certification.BoQ45DeX_248O3C.webp)
- ![CSA certification mark](https://entogo.ca/_astro/Entogo-CSA-Canadian-Standards-Association-Safety-Certification.CY1FySDR_Z11vFCD.webp)
- ![CE European Conformity marking](https://entogo.ca/_astro/Entogo-CE-European-Conformity-Marking.xJPMJKcl_1wU1NT.webp)
- ![ISO 9001 quality management mark](https://entogo.ca/_astro/Entogo-ISO-9001-Quality-Management-System-Certification.DbscJvvM_47kvy.webp)
- ![ISO 14001 environmental management mark](https://entogo.ca/_astro/Entogo-ISO-14001-Environmental-Management-System-Certification.DXOTPjd4_Z4rpDm.webp)
- ![IEC CB Scheme mark](https://entogo.ca/_astro/Entogo-CB-Scheme-IEC-International-Electrical-Certification.CPXJ4xZK_aV0YT.webp)

Built under audited ISO quality systems and to ANSI/IEEE & IEC standards. Product-level UL (cULus) / CSA certification available on request.

[See all certifications](https://entogo.ca/certifications)

## Specifications

Low-Voltage Drawout Switchgear specifications
| Specification | Value |
| --- | --- |
| Applicable standards | UL 1558 · ANSI/IEEE C37.20.1 · breakers UL 1066 (LVPCB) / UL 489 |
| Type | Low-voltage metal-enclosed drawout (withdrawable) switchgear |
| Rated voltage | ≤ 600 V (≤ 635 V per UL 1558) |
| Main bus / continuous | Up to 5000 A |
| Short-circuit withstand / SCCR | 65 / 85 / 100 kAIC, 30-cycle short-time |
| Frequency | 60 Hz |
| Functions | Power distribution, motor control, power-factor correction |
| Breakers | Drawout low-voltage power circuit breakers (LVPCB) |
| Enclosure | NEMA Type 1 (indoor) / 3R (outdoor) |

Glossary: [60 Hz vs. 50 Hz](https://entogo.ca/glossary#60-hz-vs-50-hz) [Selective coordination](https://entogo.ca/glossary#selective-coordination) [Metal-enclosed](https://entogo.ca/glossary#metal-enclosed-switchgear)

## Applications

- Data-center main / tie / feeder switchgear
- Power plants and heavy industry
- Large commercial and institutional service
- Mission-critical and high-automation facilities

Payment & financing

Flexible payment and project financing is available for qualified projects — milestone-based plans, reduced upfront terms and third-party financing. Entogo is the equipment supplier, not a lender; all options are subject to credit review and a signed agreement.

[See payment options](https://entogo.ca/payment-options)

After-sales

Backed by Entogo lifecycle service — technical support, spare parts and a minimum 36-month warranty (well beyond the industry norm; up to 10 years on major power equipment, confirmed per contract). Our team responds to every request within one business day.

[After-sales support](https://entogo.ca/support) [Track an order](https://entogo.ca/support/order-status)

FAQ

## Common questions

- **What is drawout (withdrawable) switchgear?**: Drawout switchgear mounts each power circuit breaker on a racking mechanism so it can be withdrawn to a test/disconnect position and removed for service without de-energizing the bus — the standard for mission-critical low-voltage distribution under UL 1558.
- **What ratings and standards apply?**: ≤ 600 V (≤ 635 V), up to 5000 A, 65 / 85 / 100 kAIC with 30-cycle short-time withstand, 60 Hz. Designed to UL 1558 / ANSI C37.20.1 with UL 1066 breakers; UL (cULus) / CSA certification available on request.
- **Can it include motor control and power-factor correction?**: Yes — distribution, motor-control and power-factor-correction sections can be combined in one drawout switchgear line; dedicated motor control is also offered as a UL 845 motor control center.

Distribution

## Related products

[![Entogo metal-clad medium-voltage switchgear with drawout vacuum circuit breakers](https://entogo.ca/_astro/Entogo-Armored-Removable-AC-Metal-Enclosed-Switchgear.DuhYnxGM_1rPQtT.webp) Distribution ### Metal-Clad Switchgear (Drawout MV) Metal-clad medium-voltage switchgear with drawout vacuum circuit breakers for 5/15/27/38 kV class systems, 60 Hz — compartmentalized, insulated-bus construction up to 4000 A and 50 kA, with optional arc-resistant rating. Designed to ANSI/IEEE C37.20.2; UL/CSA certifiable. View](https://entogo.ca/products/metal-clad-switchgear)[![Entogo dead-front low-voltage switchboard, UL 891 type](https://entogo.ca/_astro/Entogo-GGD-AC-Low-Voltage-Switchgear.zdOCIT9Q_6cFiL.webp) Distribution ### Low-Voltage Switchboard (UL 891) A dead-front low-voltage switchboard for ≤ 600 V, 60 Hz service-entrance and distribution — up to 6000 A and 200 kA, with group-mounted molded-case or insulated-case breakers, for commercial, institutional and industrial buildings. Designed to UL 891; UL (cULus) / CSA certifiable. View](https://entogo.ca/products/low-voltage-switchboard)[![Entogo pad-mounted ring main unit load-break switchgear, dead-front](https://entogo.ca/_astro/Entogo-Gas-Fully-Insulated-Fully-Sealed-Ring-Main-Unit.BUgYaOBQ_1CzHVw.webp) Distribution ### Pad-Mounted Switchgear (Ring Main Unit) Pad-mounted load-break switchgear (ring main unit) for underground medium-voltage distribution — 15/25/38 kV class, 200/600 A, dead-front, with SF6 or SF6-free fault-interrupting ways for utility loops, campuses and data centers, 60 Hz. Designed to IEC 62271-200 and ANSI C57.12.28; UL/CSA certifiable. View](https://entogo.ca/products/pad-mounted-switchgear-rmu)

Request a quote

## Talk to engineering about the Low-Voltage Drawout Switchgear.

[Start an inquiry](https://entogo.ca/contact)

## Structured data (JSON-LD)

```json
{"@context":"https://schema.org","@type":"Product","@id":"https://entogo.ca/products/low-voltage-drawout-switchgear/#product","url":"https://entogo.ca/products/low-voltage-drawout-switchgear/","name":"Low-Voltage Drawout Switchgear","description":"Low-voltage drawout (withdrawable) switchgear for ≤600 V, 60 Hz distribution, motor control and power-factor correction — up to 5000 A and 100 kAIC, with drawout power circuit breakers, for data centers and industry. Designed to UL 1558/ANSI C37.20.1; UL/CSA certifiable.","image":"https://entogo.ca/_astro/Entogo-GCS-Low-Voltage-Withdrawable-Switchgear.C5gfH0Qt.png","category":"Switchgear & Distribution","additionalType":"https://en.wikipedia.org/wiki/Switchgear","brand":{"@type":"Brand","name":"Entogo"},"manufacturer":{"@id":"https://entogo.ca/#organization"},"model":"≤ 600 V · up to 5000 A","additionalProperty":[{"@type":"PropertyValue","name":"Applicable standards","value":"UL 1558 · ANSI/IEEE C37.20.1 · breakers UL 1066 (LVPCB) / UL 489"},{"@type":"PropertyValue","name":"Type","value":"Low-voltage metal-enclosed drawout (withdrawable) switchgear"},{"@type":"PropertyValue","name":"Rated voltage","value":"≤ 600 V (≤ 635 V per UL 1558)"},{"@type":"PropertyValue","name":"Main bus / continuous","value":"Up to 5000 A"},{"@type":"PropertyValue","name":"Short-circuit withstand / SCCR","value":"65 / 85 / 100 kAIC, 30-cycle short-time"},{"@type":"PropertyValue","name":"Frequency","value":"60 Hz"},{"@type":"PropertyValue","name":"Functions","value":"Power distribution, motor control, power-factor correction"},{"@type":"PropertyValue","name":"Breakers","value":"Drawout low-voltage power circuit breakers (LVPCB)"},{"@type":"PropertyValue","name":"Enclosure","value":"NEMA Type 1 (indoor) / 3R (outdoor)"},{"@type":"PropertyValue","name":"Application","value":"Data-center main / tie / feeder switchgear"},{"@type":"PropertyValue","name":"Application","value":"Power plants and heavy industry"},{"@type":"PropertyValue","name":"Application","value":"Large commercial and institutional service"},{"@type":"PropertyValue","name":"Application","value":"Mission-critical and high-automation facilities"},{"@type":"PropertyValue","name":"Delivery lead time","minValue":12,"maxValue":18,"unitCode":"WEE"},{"@type":"PropertyValue","name":"Warranty (minimum)","value":36,"unitCode":"MON"}],"isRelatedTo":[{"@type":"Product","name":"Metal-Clad Switchgear (Drawout MV)","url":"https://entogo.ca/products/metal-clad-switchgear/"},{"@type":"Product","name":"Low-Voltage Switchboard (UL 891)","url":"https://entogo.ca/products/low-voltage-switchboard/"},{"@type":"Product","name":"Pad-Mounted Switchgear (Ring Main Unit)","url":"https://entogo.ca/products/pad-mounted-switchgear-rmu/"}],"potentialAction":{"@type":"QuoteAction","name":"Request a quote","target":"https://entogo.ca/contact/"}}
```

```json
{"@context":"https://schema.org","@type":"BreadcrumbList","itemListElement":[{"@type":"ListItem","position":1,"name":"Home","item":"https://entogo.ca/"},{"@type":"ListItem","position":2,"name":"Products","item":"https://entogo.ca/products/"},{"@type":"ListItem","position":3,"name":"Switchgear & Distribution","item":"https://entogo.ca/products/category/switchgear-distribution/"},{"@type":"ListItem","position":4,"name":"Low-Voltage Drawout Switchgear","item":"https://entogo.ca/products/low-voltage-drawout-switchgear/"}]}
```

```json
{"@context":"https://schema.org","@type":"FAQPage","mainEntity":[{"@type":"Question","name":"What is drawout (withdrawable) switchgear?","acceptedAnswer":{"@type":"Answer","text":"Drawout switchgear mounts each power circuit breaker on a racking mechanism so it can be withdrawn to a test/disconnect position and removed for service without de-energizing the bus — the standard for mission-critical low-voltage distribution under UL 1558."}},{"@type":"Question","name":"What ratings and standards apply?","acceptedAnswer":{"@type":"Answer","text":"≤ 600 V (≤ 635 V), up to 5000 A, 65 / 85 / 100 kAIC with 30-cycle short-time withstand, 60 Hz. Designed to UL 1558 / ANSI C37.20.1 with UL 1066 breakers; UL (cULus) / CSA certification available on request."}},{"@type":"Question","name":"Can it include motor control and power-factor correction?","acceptedAnswer":{"@type":"Answer","text":"Yes — distribution, motor-control and power-factor-correction sections can be combined in one drawout switchgear line; dedicated motor control is also offered as a UL 845 motor control center."}}]}
```

_Markdown twin of https://entogo.ca/products/low-voltage-drawout-switchgear/ — generated at build time from the same content as the HTML page. Company facts, catalogue index and contact: https://entogo.ca/llms.txt_