title: "Metal-Clad Switchgear (Drawout MV) | Entogo"
description: "Metal-clad medium-voltage switchgear with drawout vacuum circuit breakers for 5/15/27/38 kV class systems, 60 Hz — compartmentalized, insulated-bus…"
url: https://entogo.ca/products/metal-clad-switchgear/
lang: en
type: website
image: https://entogo.ca/_astro/Entogo-Armored-Removable-AC-Metal-Enclosed-Switchgear.DuhYnxGM.png
alternates:
  en: https://entogo.ca/products/metal-clad-switchgear/
  fr-CA: https://entogo.ca/fr/products/metal-clad-switchgear/
  es: https://entogo.ca/es/products/metal-clad-switchgear/
  ar: https://entogo.ca/ar/products/metal-clad-switchgear/
site: https://entogo.ca/
llms: https://entogo.ca/llms.txt
---

Home › Products › Switchgear & Distribution › Metal-Clad Switchgear (Drawout MV)

Switchgear & Distribution

# Metal-Clad Switchgear (Drawout MV)

5 / 15 / 27 / 38 kV class · up to 4000 A

![Entogo metal-clad medium-voltage switchgear with drawout vacuum circuit breakers](https://entogo.ca/_astro/Entogo-Armored-Removable-AC-Metal-Enclosed-Switchgear.DuhYnxGM_1rPQtT.webp)

Overview

Metal-clad medium-voltage switchgear with drawout vacuum circuit breakers for 5/15/27/38 kV class systems, 60 Hz — compartmentalized, insulated-bus construction up to 4000 A and 50 kA, with optional arc-resistant rating. Designed to ANSI/IEEE C37.20.2; UL/CSA certifiable.

Entogo designs and builds the Metal-Clad Switchgear (Drawout MV) in its own factory with a vertically integrated supply chain: this product ships in 16–24 weeks (new UL or CSA certification can extend that, within a guaranteed 36-week worst case), and every Entogo product carries a minimum 36-month manufacturer warranty.

This **metal-clad medium-voltage switchgear** is built for breaker-protected primary distribution: drawout vacuum circuit breakers, insulated and isolated bus, and grounded steel barriers between each compartment for operator safety. It serves **5 / 15 / 27 / 38 kV class** systems at 60 Hz, with main bus ratings to **4000 A** and interrupting ratings up to **50 kA** (63 kA available).

Configuration is specified per project — voltage class and BIL, continuous and interrupting current, breaker and relay scheme, optional arc-resistant Type 2B accessibility, and **NEMA 1** indoor or **3R** outdoor enclosure. Designed and built to **ANSI/IEEE C37.20.2** with breakers to C37.04 / C37.06 / C37.09, it is SCADA-ready for utility substations, data-center electrical rooms and industrial primary feeders. UL / CSA certification is available on request.

## Key features

- Metal-clad construction — drawout breakers, insulated/isolated bus and grounded steel barriers between compartments for operator safety.
- Designed and built to ANSI/IEEE C37.20.2, with breakers to C37.04 / C37.06 / C37.09, 60 Hz — UL / CSA certification available on request.
- 5 / 15 / 27 / 38 kV class, up to 4000 A continuous and 50 kA (63 kA available) interrupting.
- Optional arc-resistant accessibility Type 2B per IEEE C37.20.7.
- NEMA 1 indoor or 3R outdoor enclosure; SCADA-ready protection and metering.

Custom-engineered · built to order

[Get a quote](https://entogo.ca/contact/)

Lead time

16–24 weeks

Order now for estimated delivery Jan 2027 – Mar 2027.

Certification / testing may extend this per the standard and scope.

Quality & certifications

- ![UL safety certification mark](https://entogo.ca/_astro/Entogo-UL-Underwriters-Laboratories-North-America-Safety-Certification.BoQ45DeX_248O3C.webp)
- ![CSA certification mark](https://entogo.ca/_astro/Entogo-CSA-Canadian-Standards-Association-Safety-Certification.CY1FySDR_Z11vFCD.webp)
- ![CE European Conformity marking](https://entogo.ca/_astro/Entogo-CE-European-Conformity-Marking.xJPMJKcl_1wU1NT.webp)
- ![ISO 9001 quality management mark](https://entogo.ca/_astro/Entogo-ISO-9001-Quality-Management-System-Certification.DbscJvvM_47kvy.webp)
- ![ISO 14001 environmental management mark](https://entogo.ca/_astro/Entogo-ISO-14001-Environmental-Management-System-Certification.DXOTPjd4_Z4rpDm.webp)
- ![IEC CB Scheme mark](https://entogo.ca/_astro/Entogo-CB-Scheme-IEC-International-Electrical-Certification.CPXJ4xZK_aV0YT.webp)

Built under audited ISO quality systems and to ANSI/IEEE & IEC standards. Product-level UL (cULus) / CSA certification available on request.

[See all certifications](https://entogo.ca/certifications/)

## Specifications

Metal-Clad Switchgear (Drawout MV) specifications
| Specification | Value |
| --- | --- |
| Applicable standards | ANSI/IEEE C37.20.2 (assembly) · C37.04 / C37.06 / C37.09 (breakers) · C37.20.7 (arc-resistant) |
| Construction | Metal-clad — compartmentalized, drawout breaker, insulated bus, grounded barriers |
| Rated max voltage | 4.76 / 8.25 / 15 / 27 / 38 kV |
| BIL | 60 / 95 / 125 / 150 kV by class |
| Continuous (main bus) | 1200 / 2000 / 3000 A (to 4000 A) |
| Short-circuit / interrupting | Up to 40 / 50 kA symmetrical (63 kA available) |
| Frequency | 60 Hz |
| Breaker | Drawout vacuum circuit breaker |
| Arc-resistant | Optional Type 2B per IEEE C37.20.7 |
| Enclosure | NEMA Type 1 (indoor) / 3R (outdoor) |

Glossary: [60 Hz vs. 50 Hz](https://entogo.ca/glossary/#60-hz-vs-50-hz) [Arc-resistant switchgear](https://entogo.ca/glossary/#arc-resistant-switchgear) [Voltage class](https://entogo.ca/glossary/#voltage-class)

## Applications

- Utility and industrial primary substations
- Data-center medium-voltage electrical rooms
- Renewable-energy and battery-storage interconnection
- Large commercial and campus MV distribution

Payment & financing

Flexible payment and project financing is available for qualified projects — milestone-based plans, reduced upfront terms and third-party financing. Entogo is the equipment supplier, not a lender; all options are subject to credit review and a signed agreement.

[See payment options](https://entogo.ca/payment-options/)

After-sales

Backed by Entogo lifecycle service — technical support, spare parts and a minimum 36-month warranty (well beyond the industry norm; up to 10 years on major power equipment, confirmed per contract). Our team responds to every request within one business day.

[After-sales support](https://entogo.ca/support/) [Track an order](https://entogo.ca/support/order-status/)

FAQ

## Common questions

- **What is the difference between metal-clad and metal-enclosed switchgear?**: Metal-clad switchgear (ANSI/IEEE C37.20.2) uses drawout circuit breakers, insulated bus and grounded steel barriers between every major compartment — a higher tier than metal-enclosed (C37.20.3) load-interrupter gear. Choose metal-clad for breaker-protected primary distribution.
- **What voltage classes and ratings are available?**: 4.76 / 8.25 / 15 / 27 / 38 kV (60 / 95 / 125 / 150 kV BIL), 1200 – 4000 A main bus, up to 50 kA (63 kA available) interrupting, 60 Hz — with an optional arc-resistant Type 2B rating.
- **Is it UL listed or CSA certified?**: Units are designed and built to ANSI/IEEE C37.20.2 and the C37.04 / .06 / .09 breaker standards. UL / CSA certification is available on request, with certified assemblies shipping within a guaranteed 36-week worst case.

Distribution

## Related products

[![Entogo dead-front low-voltage switchboard, UL 891 type](https://entogo.ca/_astro/Entogo-GGD-AC-Low-Voltage-Switchgear.zdOCIT9Q_6cFiL.webp) Distribution ### Low-Voltage Switchboard (UL 891) A dead-front low-voltage switchboard for ≤ 600 V, 60 Hz service-entrance and distribution — up to 6000 A and 200 kA, with group-mounted molded-case or insulated-case breakers, for commercial, institutional and industrial buildings. Designed to UL 891; UL (cULus) / CSA certifiable. View](https://entogo.ca/products/low-voltage-switchboard/)[![Entogo pad-mounted ring main unit load-break switchgear, dead-front](https://entogo.ca/_astro/Entogo-Gas-Fully-Insulated-Fully-Sealed-Ring-Main-Unit.BUgYaOBQ_1CzHVw.webp) Distribution ### Pad-Mounted Switchgear (Ring Main Unit) Pad-mounted load-break switchgear (ring main unit) for underground medium-voltage distribution — 15/25/38 kV class, 200/600 A, dead-front, with SF6 or SF6-free fault-interrupting ways for utility loops, campuses and data centers, 60 Hz. Designed to IEC 62271-200 and ANSI C57.12.28; UL/CSA certifiable. View](https://entogo.ca/products/pad-mounted-switchgear-rmu/)[![Entogo metal-enclosed load-interrupter medium-voltage switchgear](https://entogo.ca/_astro/Entogo-Box-Type-Fixed-Metal-Enclosed-Switchgear.Cc7QCP4l_1y87ft.webp) Distribution ### Metal-Enclosed Load-Interrupter Switchgear Metal-enclosed load-interrupter switchgear for 15 / 27 / 38 kV class medium-voltage systems, 60 Hz — fixed-mounted load-break switches with power-fuse protection in a compact steel enclosure, for compact substations, primary service entrance and MV isolation. Designed to ANSI/IEEE C37.20.3; UL / CSA certifiable. View](https://entogo.ca/products/metal-enclosed-switchgear/)

Request a quote

## Talk to engineering about the Metal-Clad Switchgear (Drawout MV).

[Start an inquiry](https://entogo.ca/contact/)

## Structured data (JSON-LD)

```json
{"@context":"https://schema.org","@type":"Product","@id":"https://entogo.ca/products/metal-clad-switchgear/#product","url":"https://entogo.ca/products/metal-clad-switchgear/","name":"Metal-Clad Switchgear (Drawout MV)","description":"Metal-clad medium-voltage switchgear with drawout vacuum circuit breakers for 5/15/27/38 kV class systems, 60 Hz — compartmentalized, insulated-bus construction up to 4000 A and 50 kA, with optional arc-resistant rating. Designed to ANSI/IEEE C37.20.2; UL/CSA certifiable.","image":"https://entogo.ca/_astro/Entogo-Armored-Removable-AC-Metal-Enclosed-Switchgear.DuhYnxGM.png","category":"Switchgear & Distribution","additionalType":"https://en.wikipedia.org/wiki/Switchgear","brand":{"@type":"Brand","name":"Entogo"},"manufacturer":{"@id":"https://entogo.ca/#organization"},"model":"5 / 15 / 27 / 38 kV class · up to 4000 A","additionalProperty":[{"@type":"PropertyValue","name":"Applicable standards","value":"ANSI/IEEE C37.20.2 (assembly) · C37.04 / C37.06 / C37.09 (breakers) · C37.20.7 (arc-resistant)"},{"@type":"PropertyValue","name":"Construction","value":"Metal-clad — compartmentalized, drawout breaker, insulated bus, grounded barriers"},{"@type":"PropertyValue","name":"Rated max voltage","value":"4.76 / 8.25 / 15 / 27 / 38 kV"},{"@type":"PropertyValue","name":"BIL","value":"60 / 95 / 125 / 150 kV by class"},{"@type":"PropertyValue","name":"Continuous (main bus)","value":"1200 / 2000 / 3000 A (to 4000 A)"},{"@type":"PropertyValue","name":"Short-circuit / interrupting","value":"Up to 40 / 50 kA symmetrical (63 kA available)"},{"@type":"PropertyValue","name":"Frequency","value":"60 Hz"},{"@type":"PropertyValue","name":"Breaker","value":"Drawout vacuum circuit breaker"},{"@type":"PropertyValue","name":"Arc-resistant","value":"Optional Type 2B per IEEE C37.20.7"},{"@type":"PropertyValue","name":"Enclosure","value":"NEMA Type 1 (indoor) / 3R (outdoor)"},{"@type":"PropertyValue","name":"Application","value":"Utility and industrial primary substations"},{"@type":"PropertyValue","name":"Application","value":"Data-center medium-voltage electrical rooms"},{"@type":"PropertyValue","name":"Application","value":"Renewable-energy and battery-storage interconnection"},{"@type":"PropertyValue","name":"Application","value":"Large commercial and campus MV distribution"},{"@type":"PropertyValue","name":"Delivery lead time","minValue":16,"maxValue":24,"unitCode":"WEE"},{"@type":"PropertyValue","name":"Warranty (minimum)","value":36,"unitCode":"MON"}],"isRelatedTo":[{"@type":"Product","name":"Low-Voltage Switchboard (UL 891)","url":"https://entogo.ca/products/low-voltage-switchboard/"},{"@type":"Product","name":"Pad-Mounted Switchgear (Ring Main Unit)","url":"https://entogo.ca/products/pad-mounted-switchgear-rmu/"},{"@type":"Product","name":"Metal-Enclosed Load-Interrupter Switchgear","url":"https://entogo.ca/products/metal-enclosed-switchgear/"}],"potentialAction":{"@type":"QuoteAction","name":"Request a quote","target":"https://entogo.ca/contact/"}}
```

```json
{"@context":"https://schema.org","@type":"BreadcrumbList","itemListElement":[{"@type":"ListItem","position":1,"name":"Home","item":"https://entogo.ca/"},{"@type":"ListItem","position":2,"name":"Products","item":"https://entogo.ca/products/"},{"@type":"ListItem","position":3,"name":"Switchgear & Distribution","item":"https://entogo.ca/products/category/switchgear-distribution/"},{"@type":"ListItem","position":4,"name":"Metal-Clad Switchgear (Drawout MV)","item":"https://entogo.ca/products/metal-clad-switchgear/"}]}
```

```json
{"@context":"https://schema.org","@type":"FAQPage","mainEntity":[{"@type":"Question","name":"What is the difference between metal-clad and metal-enclosed switchgear?","acceptedAnswer":{"@type":"Answer","text":"Metal-clad switchgear (ANSI/IEEE C37.20.2) uses drawout circuit breakers, insulated bus and grounded steel barriers between every major compartment — a higher tier than metal-enclosed (C37.20.3) load-interrupter gear. Choose metal-clad for breaker-protected primary distribution."}},{"@type":"Question","name":"What voltage classes and ratings are available?","acceptedAnswer":{"@type":"Answer","text":"4.76 / 8.25 / 15 / 27 / 38 kV (60 / 95 / 125 / 150 kV BIL), 1200 – 4000 A main bus, up to 50 kA (63 kA available) interrupting, 60 Hz — with an optional arc-resistant Type 2B rating."}},{"@type":"Question","name":"Is it UL listed or CSA certified?","acceptedAnswer":{"@type":"Answer","text":"Units are designed and built to ANSI/IEEE C37.20.2 and the C37.04 / .06 / .09 breaker standards. UL / CSA certification is available on request, with certified assemblies shipping within a guaranteed 36-week worst case."}}]}
```

_Markdown twin of https://entogo.ca/products/metal-clad-switchgear/ — generated at build time from the same content as the HTML page. Company facts, catalogue index and contact: https://entogo.ca/llms.txt_