title: "Automatic Power-Factor-Correction Capacitor Bank | Entogo"
description: "An automatic power-factor-correction (PFC) capacitor bank for 480 V, 60 Hz systems — stepped, controller-switched kVAR with detuned harmonic-filter…"
url: https://entogo.ca/products/power-factor-correction-capacitor-bank/
lang: en
type: website
image: https://entogo.ca/_astro/Entogo-Low-Voltage-Reactive-Power-Compensation-Cabinet.2RVOaNzv.png
alternates:
  en: https://entogo.ca/products/power-factor-correction-capacitor-bank/
  fr-CA: https://entogo.ca/fr/products/power-factor-correction-capacitor-bank/
  es: https://entogo.ca/es/products/power-factor-correction-capacitor-bank/
  ar: https://entogo.ca/ar/products/power-factor-correction-capacitor-bank/
site: https://entogo.ca/
llms: https://entogo.ca/llms.txt
---

Home › Products › Switchgear & Distribution › Automatic Power-Factor-Correction Capacitor Bank

Switchgear & Distribution

# Automatic Power-Factor-Correction Capacitor Bank

480 V · stepped / detuned

![Entogo automatic power-factor-correction capacitor bank](https://entogo.ca/_astro/Entogo-Low-Voltage-Reactive-Power-Compensation-Cabinet.2RVOaNzv_ZsiHQU.webp)

Overview

An automatic power-factor-correction (PFC) capacitor bank for 480 V, 60 Hz systems — stepped, controller-switched kVAR with detuned harmonic-filter reactors to raise power factor, cut demand charges and free transformer capacity. Designed to UL 810, IEEE 18 and NEMA CP-1; UL/CSA certifiable.

Entogo designs and builds the Automatic Power-Factor-Correction Capacitor Bank in its own factory with a vertically integrated supply chain: this product ships in 12–18 weeks (new UL or CSA certification can extend that, within a guaranteed 36-week worst case), and every Entogo product carries a minimum 36-month manufacturer warranty.

This **automatic power-factor-correction capacitor bank** raises the power factor of **480 V**, 60 Hz loads — switching stepped kVAR in and out under a PF controller to cut utility demand and reactive charges and free real capacity in transformers and feeders. Detuned filter reactors (typically 7% or 14%) suppress harmonics and protect the capacitors on VFD-heavy and other non-linear systems.

Contactor switching is standard, with thyristor / dynamic switching available where speed and service life matter, in **NEMA 1** indoor or **3R** outdoor enclosures sized to the load. Designed and built to **UL 810**, **ANSI/IEEE 18** and NEMA CP-1 and installed per the NEC, with UL (cULus) / CSA certification available on request.

## Key features

- Raises power factor, cuts utility demand / reactive charges and frees real transformer and feeder capacity.
- Designed and built to UL 810, ANSI/IEEE 18 and NEMA CP-1, installed per NEC, 60 Hz — UL (cULus) / CSA certification available on request.
- Detuned filter reactors suppress harmonics and protect capacitors on non-linear (VFD-heavy) systems.
- Automatic PF controller with contactor switching; thyristor / dynamic switching optional for fast, durable response.
- NEMA 1 indoor or 3R outdoor; stepped kVAR sized to the load.

Custom-engineered · built to order

[Get a quote](https://entogo.ca/contact)

Lead time

12–18 weeks

Order now for estimated delivery Dec 2026 – Jan 2027.

Certification / testing may extend this per the standard and scope.

Quality & certifications

- ![UL safety certification mark](https://entogo.ca/_astro/Entogo-UL-Underwriters-Laboratories-North-America-Safety-Certification.BoQ45DeX_248O3C.webp)
- ![CSA certification mark](https://entogo.ca/_astro/Entogo-CSA-Canadian-Standards-Association-Safety-Certification.CY1FySDR_Z11vFCD.webp)
- ![CE European Conformity marking](https://entogo.ca/_astro/Entogo-CE-European-Conformity-Marking.xJPMJKcl_1wU1NT.webp)
- ![ISO 9001 quality management mark](https://entogo.ca/_astro/Entogo-ISO-9001-Quality-Management-System-Certification.DbscJvvM_47kvy.webp)
- ![ISO 14001 environmental management mark](https://entogo.ca/_astro/Entogo-ISO-14001-Environmental-Management-System-Certification.DXOTPjd4_Z4rpDm.webp)
- ![IEC CB Scheme mark](https://entogo.ca/_astro/Entogo-CB-Scheme-IEC-International-Electrical-Certification.CPXJ4xZK_aV0YT.webp)

Built under audited ISO quality systems and to ANSI/IEEE & IEC standards. Product-level UL (cULus) / CSA certification available on request.

[See all certifications](https://entogo.ca/certifications)

## Specifications

Automatic Power-Factor-Correction Capacitor Bank specifications
| Specification | Value |
| --- | --- |
| Applicable standards | UL 810 (capacitors) · ANSI/IEEE 18 · NEMA CP-1 · installed per NEC |
| Type | Automatic (stepped) power-factor-correction capacitor bank |
| Rated voltage | 480 V (240 / 600 V available) |
| Compensation | Stepped kVAR, controller-switched (e.g. 50 – 600 kVAR) |
| Harmonic control | Detuned filter reactors (e.g. 7 % / 14 %) |
| Switching | PF controller + contactors (thyristor / dynamic option) |
| Frequency | 60 Hz |
| Enclosure | NEMA Type 1 (indoor) / 3R (outdoor) |

Glossary: [Power-factor-correction capacitor bank](https://entogo.ca/glossary#power-factor-correction) [60 Hz vs. 50 Hz](https://entogo.ca/glossary#60-hz-vs-50-hz)

## Applications

- Industrial power-factor correction and demand-charge reduction
- Harmonic mitigation on VFD / non-linear loads
- Transformer and feeder capacity recovery
- Commercial and institutional power quality

Payment & financing

Flexible payment and project financing is available for qualified projects — milestone-based plans, reduced upfront terms and third-party financing. Entogo is the equipment supplier, not a lender; all options are subject to credit review and a signed agreement.

[See payment options](https://entogo.ca/payment-options)

After-sales

Backed by Entogo lifecycle service — technical support, spare parts and a minimum 36-month warranty (well beyond the industry norm; up to 10 years on major power equipment, confirmed per contract). Our team responds to every request within one business day.

[After-sales support](https://entogo.ca/support) [Track an order](https://entogo.ca/support/order-status)

FAQ

## Common questions

- **Why install a power-factor-correction capacitor bank?**: Correcting power factor reduces reactive current, which lowers utility demand/reactive charges, frees real capacity in transformers and feeders, and improves voltage. An automatic (stepped) bank switches kVAR in and out to match the load.
- **Do I need detuned reactors?**: On systems with significant harmonic content (VFDs, rectifiers), detuned filter reactors (typically 7% or 14%) are recommended to suppress harmonics and protect the capacitors. They are available as part of the bank.
- **What standards and ratings apply?**: 480 V (240 / 600 V available), stepped kVAR with PF controller, 60 Hz. Designed to UL 810, ANSI/IEEE 18 and NEMA CP-1, installed per NEC; UL (cULus) / CSA certification available on request.

Distribution

## Related products

[![Entogo metal-clad medium-voltage switchgear with drawout vacuum circuit breakers](https://entogo.ca/_astro/Entogo-Armored-Removable-AC-Metal-Enclosed-Switchgear.DuhYnxGM_1rPQtT.webp) Distribution ### Metal-Clad Switchgear (Drawout MV) Metal-clad medium-voltage switchgear with drawout vacuum circuit breakers for 5/15/27/38 kV class systems, 60 Hz — compartmentalized, insulated-bus construction up to 4000 A and 50 kA, with optional arc-resistant rating. Designed to ANSI/IEEE C37.20.2; UL/CSA certifiable. View](https://entogo.ca/products/metal-clad-switchgear)[![Entogo dead-front low-voltage switchboard, UL 891 type](https://entogo.ca/_astro/Entogo-GGD-AC-Low-Voltage-Switchgear.zdOCIT9Q_6cFiL.webp) Distribution ### Low-Voltage Switchboard (UL 891) A dead-front low-voltage switchboard for ≤ 600 V, 60 Hz service-entrance and distribution — up to 6000 A and 200 kA, with group-mounted molded-case or insulated-case breakers, for commercial, institutional and industrial buildings. Designed to UL 891; UL (cULus) / CSA certifiable. View](https://entogo.ca/products/low-voltage-switchboard)[![Entogo pad-mounted ring main unit load-break switchgear, dead-front](https://entogo.ca/_astro/Entogo-Gas-Fully-Insulated-Fully-Sealed-Ring-Main-Unit.BUgYaOBQ_1CzHVw.webp) Distribution ### Pad-Mounted Switchgear (Ring Main Unit) Pad-mounted load-break switchgear (ring main unit) for underground medium-voltage distribution — 15/25/38 kV class, 200/600 A, dead-front, with SF6 or SF6-free fault-interrupting ways for utility loops, campuses and data centers, 60 Hz. Designed to IEC 62271-200 and ANSI C57.12.28; UL/CSA certifiable. View](https://entogo.ca/products/pad-mounted-switchgear-rmu)

Request a quote

## Talk to engineering about the Automatic Power-Factor-Correction Capacitor Bank.

[Start an inquiry](https://entogo.ca/contact)

## Structured data (JSON-LD)

```json
{"@context":"https://schema.org","@type":"Product","@id":"https://entogo.ca/products/power-factor-correction-capacitor-bank/#product","url":"https://entogo.ca/products/power-factor-correction-capacitor-bank/","name":"Automatic Power-Factor-Correction Capacitor Bank","description":"An automatic power-factor-correction (PFC) capacitor bank for 480 V, 60 Hz systems — stepped, controller-switched kVAR with detuned harmonic-filter reactors to raise power factor, cut demand charges and free transformer capacity. Designed to UL 810, IEEE 18 and NEMA CP-1; UL/CSA certifiable.","image":"https://entogo.ca/_astro/Entogo-Low-Voltage-Reactive-Power-Compensation-Cabinet.2RVOaNzv.png","category":"Switchgear & Distribution","additionalType":"https://en.wikipedia.org/wiki/Switchgear","brand":{"@type":"Brand","name":"Entogo"},"manufacturer":{"@id":"https://entogo.ca/#organization"},"model":"480 V · stepped / detuned","additionalProperty":[{"@type":"PropertyValue","name":"Applicable standards","value":"UL 810 (capacitors) · ANSI/IEEE 18 · NEMA CP-1 · installed per NEC"},{"@type":"PropertyValue","name":"Type","value":"Automatic (stepped) power-factor-correction capacitor bank"},{"@type":"PropertyValue","name":"Rated voltage","value":"480 V (240 / 600 V available)"},{"@type":"PropertyValue","name":"Compensation","value":"Stepped kVAR, controller-switched (e.g. 50 – 600 kVAR)"},{"@type":"PropertyValue","name":"Harmonic control","value":"Detuned filter reactors (e.g. 7 % / 14 %)"},{"@type":"PropertyValue","name":"Switching","value":"PF controller + contactors (thyristor / dynamic option)"},{"@type":"PropertyValue","name":"Frequency","value":"60 Hz"},{"@type":"PropertyValue","name":"Enclosure","value":"NEMA Type 1 (indoor) / 3R (outdoor)"},{"@type":"PropertyValue","name":"Application","value":"Industrial power-factor correction and demand-charge reduction"},{"@type":"PropertyValue","name":"Application","value":"Harmonic mitigation on VFD / non-linear loads"},{"@type":"PropertyValue","name":"Application","value":"Transformer and feeder capacity recovery"},{"@type":"PropertyValue","name":"Application","value":"Commercial and institutional power quality"},{"@type":"PropertyValue","name":"Delivery lead time","minValue":12,"maxValue":18,"unitCode":"WEE"},{"@type":"PropertyValue","name":"Warranty (minimum)","value":36,"unitCode":"MON"}],"isRelatedTo":[{"@type":"Product","name":"Metal-Clad Switchgear (Drawout MV)","url":"https://entogo.ca/products/metal-clad-switchgear/"},{"@type":"Product","name":"Low-Voltage Switchboard (UL 891)","url":"https://entogo.ca/products/low-voltage-switchboard/"},{"@type":"Product","name":"Pad-Mounted Switchgear (Ring Main Unit)","url":"https://entogo.ca/products/pad-mounted-switchgear-rmu/"}],"potentialAction":{"@type":"QuoteAction","name":"Request a quote","target":"https://entogo.ca/contact/"}}
```

```json
{"@context":"https://schema.org","@type":"BreadcrumbList","itemListElement":[{"@type":"ListItem","position":1,"name":"Home","item":"https://entogo.ca/"},{"@type":"ListItem","position":2,"name":"Products","item":"https://entogo.ca/products/"},{"@type":"ListItem","position":3,"name":"Switchgear & Distribution","item":"https://entogo.ca/products/category/switchgear-distribution/"},{"@type":"ListItem","position":4,"name":"Automatic Power-Factor-Correction Capacitor Bank","item":"https://entogo.ca/products/power-factor-correction-capacitor-bank/"}]}
```

```json
{"@context":"https://schema.org","@type":"FAQPage","mainEntity":[{"@type":"Question","name":"Why install a power-factor-correction capacitor bank?","acceptedAnswer":{"@type":"Answer","text":"Correcting power factor reduces reactive current, which lowers utility demand/reactive charges, frees real capacity in transformers and feeders, and improves voltage. An automatic (stepped) bank switches kVAR in and out to match the load."}},{"@type":"Question","name":"Do I need detuned reactors?","acceptedAnswer":{"@type":"Answer","text":"On systems with significant harmonic content (VFDs, rectifiers), detuned filter reactors (typically 7% or 14%) are recommended to suppress harmonics and protect the capacitors. They are available as part of the bank."}},{"@type":"Question","name":"What standards and ratings apply?","acceptedAnswer":{"@type":"Answer","text":"480 V (240 / 600 V available), stepped kVAR with PF controller, 60 Hz. Designed to UL 810, ANSI/IEEE 18 and NEMA CP-1, installed per NEC; UL (cULus) / CSA certification available on request."}}]}
```

_Markdown twin of https://entogo.ca/products/power-factor-correction-capacitor-bank/ — generated at build time from the same content as the HTML page. Company facts, catalogue index and contact: https://entogo.ca/llms.txt_