title: "Step Voltage Regulator (SVR) | Entogo"
description: "Entogo supplies step voltage regulators for feeder voltage control. Reference configurations span 2.5–19.92 kV."
url: https://entogo.ca/products/step-voltage-regulator/
lang: en
type: website
image: https://entogo.ca/_astro/step-voltage-regulator.Ci6fH5B-.webp
alternates:
  en: https://entogo.ca/products/step-voltage-regulator/
  fr-CA: https://entogo.ca/fr/products/step-voltage-regulator/
  fr: https://entogo.ca/fr/products/step-voltage-regulator/
  es: https://entogo.ca/es/products/step-voltage-regulator/
  ar: https://entogo.ca/ar/products/step-voltage-regulator/
  pl: https://entogo.ca/pl/products/step-voltage-regulator/
  ro: https://entogo.ca/ro/products/step-voltage-regulator/
  ru-KZ: https://entogo.ca/ru/products/step-voltage-regulator/
  ru-UZ: https://entogo.ca/ru/products/step-voltage-regulator/
  ru-KG: https://entogo.ca/ru/products/step-voltage-regulator/
  ru-TJ: https://entogo.ca/ru/products/step-voltage-regulator/
  ru-TM: https://entogo.ca/ru/products/step-voltage-regulator/
  ru-AZ: https://entogo.ca/ru/products/step-voltage-regulator/
  ru-AM: https://entogo.ca/ru/products/step-voltage-regulator/
  ru-GE: https://entogo.ca/ru/products/step-voltage-regulator/
site: https://entogo.ca/
llms: https://entogo.ca/llms.txt
---

Products › Voltage Regulation & Power Quality › Step Voltage Regulator (SVR)

Voltage Regulation & Power Quality

# Step Voltage Regulator (SVR)

![Step Voltage Regulator (SVR)](https://entogo.ca/_astro/step-voltage-regulator.Ci6fH5B-_6gguI.webp)

Representative configuration. The offered model, dimensions and interfaces are confirmed with the technical proposal.

Overview

Entogo supplies step voltage regulators for feeder voltage control. Reference configurations span 2.5–19.92 kV; select line current, insulation, connection and controller together rather than treating regulator kVA as total feeder capacity.

Entogo supplies this project equipment through manufacturing partners. Entogo Inc. in Toronto coordinates technical selection, supply scope and order support.

| Specification | Value |
| --- | --- |
| Construction | Liquid-immersed single-phase feeder regulator with tap controller |
| Reference voltage ratings | 2.5 / 5 / 7.62 / 13.8 / 19.92 kV; winding connection to confirm |
| Frequency | 50 / 60 Hz configurations |
| Reference operating point | 13.8 kV, 200 A, 276 kVA regulator rating |
| Insulation example | 13.8 kV reference row: 95 kV BIL |
| Control specification | Setpoint, bandwidth, time delay and line-drop compensation |
| Network duty | Forward/reverse power-flow mode and bypass arrangement to agree |
| Design reference | IEC/IEEE 60076-21, including the associated controller |

Reference configurations and selection criteria are shown together. The technical offer defines the matched ratings, tests and guaranteed performance for the ordered unit.

## Read the regulator rating correctly

The reference table pairs 13.8 kV and 200 A with a 276 kVA regulation rating. The single-phase through-load apparent power at that operating point is 2,760 kVA; the two figures describe different duties. Do not size a feeder by the regulation-kVA label alone.

Check connection, insulation and current together. A three-phase bank also needs an agreed connection and control strategy; it is not defined by ordering three identical cans.

## Applications

- Distribution feeders
- Network voltage management
- Utility upgrades

## Selection & project requirements

- **Why does 13.8 kV at 200 A show a 276 kVA regulator rating?**: The 276 kVA entry is regulation capacity, not the total power passing through the feeder. At 13.8 kV and 200 A the single-phase through-load figure is 2,760 kVA. Confirm the regulation range and bank connection for the order.
- **Can a feeder with solar export use the same controller settings?**: Not automatically. Reverse power flow changes the control problem. Define forward/reverse sensing, line-drop compensation, bandwidth and time delay from the feeder study, especially where generation and capacitor controls interact.
- **Is a feeder regulator interchangeable with an industrial AVR?**: No. A feeder regulator is selected for network voltage, line current, insulation and feeder control. A low-voltage stabilizer serves connected loads. They address different installation and operating duties.
- **How should a North-American utility specify the unit?**: Provide its regulator specification, rated winding connection, insulation level, current, bypass scheme and controller/communications requirements. IEC/IEEE 60076-21 is a design reference; utility acceptance and the exact test schedule still need agreement.

For Canadian and US projects, include the utility specification, service frequency and required approvals. State whether the order is for the transformer alone or an integrated equipment package.

## Discuss your equipment requirements

Send your single-line diagram, load or process data, target market and required schedule. We will identify the configuration and documents needed for a technical quotation.

## Design references

[![Power transformer at an electrical substation with an on-load tap changer for voltage regulation](https://entogo.ca/_astro/transformer-voltage-regulation-tap-changers.LSKEj7V-_xljGw.webp) Power & Distribution ### De-energized taps or a load tap changer? Specifying transformer voltage regulation Transformer regulation is %R cos θ + %X sin θ plus a small quadratic term. A 1500 kVA, 5.75 %Z unit at 0.85 PF drops 3.85 %, so a 13.3 to 14.0 kV primary needs the 13 455 V tap to hold 456 to 504 V. The full ANSI C84.1 Range A primary swing needs an OLTC or a step regulator. View](https://entogo.ca/insights/transformer-voltage-regulation-tap-changers/)

## Related equipment

[![Entogo automatic power-factor-correction capacitor bank](https://entogo.ca/_astro/Entogo-Low-Voltage-Reactive-Power-Compensation-Cabinet.2RVOaNzv_ZsiHQU.webp) Products ### Automatic Power-Factor-Correction Capacitor Bank An automatic power-factor-correction (PFC) capacitor bank for 480 V, 60 Hz systems — stepped, controller-switched kVAR with detuned harmonic-filter reactors to raise power factor, cut demand charges and free up transformer capacity. Designed to UL 810, IEEE 18 and NEMA CP-1; UL/CSA certifiable. View](https://entogo.ca/products/power-factor-correction-capacitor-bank/)[![Automatic Voltage Stabilizer (AVR)](https://entogo.ca/_astro/automatic-voltage-stabilizer.Y3f17WR8_1cqfMM.webp) Products ### Automatic Voltage Stabilizer (AVR) Entogo supplies industrial automatic voltage stabilizers for loads exposed to supply variation. Specify the full input-voltage range, output tolerance, load current, starting duty and bypass arrangement before selecting the kVA. View](https://entogo.ca/products/automatic-voltage-stabilizer/)[![Entogo BWG new-energy grid-connection cabinet](https://entogo.ca/_astro/Entogo-New-Energy-Grid-Connection-Cabinet.DP_-zOW4_1JIz5i.webp) Products ### BWG New-Energy Grid-Connection Cabinet The BWG grid-connection cabinet sits between PV inverters (or an AC combiner box) and the grid in high-power photovoltaic plants, providing undervoltage/overvoltage, surge, overcurrent and grid-isolation protection with multi-function metering and anti-islanding support. View](https://entogo.ca/products/new-energy-grid-connection-cabinet/)[![Dead Tank Circuit Breaker](https://entogo.ca/_astro/dead-tank-circuit-breaker.BA5Nfi_h_mU0IX.webp) Products ### Dead Tank Circuit Breaker Entogo supplies outdoor dead-tank circuit breakers for substation switching and protection. A 72.5 kV SF6 configuration is a reference enquiry point; continuous current, breaking duty, insulation and site conditions are specified together. View](https://entogo.ca/products/dead-tank-circuit-breaker/)

## Structured data (JSON-LD)

```json
{"@context":"https://schema.org","@type":"Product","@id":"https://entogo.ca/products/step-voltage-regulator/#product","url":"https://entogo.ca/products/step-voltage-regulator/","name":"Step Voltage Regulator (SVR)","description":"Entogo supplies step voltage regulators for feeder voltage control. Reference configurations span 2.5–19.92 kV; select line current, insulation, connection and controller together rather than treating regulator kVA as total feeder capacity.","image":"https://entogo.ca/_astro/step-voltage-regulator.Ci6fH5B-.webp","potentialAction":{"@type":"QuoteAction","target":"https://entogo.ca/products/step-voltage-regulator/#quote","recipient":{"@id":"https://entogo.ca/#organization"}},"additionalProperty":[{"@type":"PropertyValue","name":"Supply model","value":"Partner-supplied project equipment"},{"@type":"PropertyValue","name":"Construction","value":"Liquid-immersed single-phase feeder regulator with tap controller"},{"@type":"PropertyValue","name":"Reference voltage ratings","value":"2.5 / 5 / 7.62 / 13.8 / 19.92 kV; winding connection to confirm"},{"@type":"PropertyValue","name":"Frequency","value":"50 / 60 Hz configurations"},{"@type":"PropertyValue","name":"Reference operating point","value":"13.8 kV, 200 A, 276 kVA regulator rating"},{"@type":"PropertyValue","name":"Insulation example","value":"13.8 kV reference row: 95 kV BIL"},{"@type":"PropertyValue","name":"Control specification","value":"Setpoint, bandwidth, time delay and line-drop compensation"},{"@type":"PropertyValue","name":"Network duty","value":"Forward/reverse power-flow mode and bypass arrangement to agree"},{"@type":"PropertyValue","name":"Design reference","value":"IEC/IEEE 60076-21, including the associated controller"}]}
```

```json
{"@context":"https://schema.org","@type":"FAQPage","mainEntity":[{"@type":"Question","name":"Why does 13.8 kV at 200 A show a 276 kVA regulator rating?","acceptedAnswer":{"@type":"Answer","text":"The 276 kVA entry is regulation capacity, not the total power passing through the feeder. At 13.8 kV and 200 A the single-phase through-load figure is 2,760 kVA. Confirm the regulation range and bank connection for the order."}},{"@type":"Question","name":"Can a feeder with solar export use the same controller settings?","acceptedAnswer":{"@type":"Answer","text":"Not automatically. Reverse power flow changes the control problem. Define forward/reverse sensing, line-drop compensation, bandwidth and time delay from the feeder study, especially where generation and capacitor controls interact."}},{"@type":"Question","name":"Is a feeder regulator interchangeable with an industrial AVR?","acceptedAnswer":{"@type":"Answer","text":"No. A feeder regulator is selected for network voltage, line current, insulation and feeder control. A low-voltage stabilizer serves connected loads. They address different installation and operating duties."}},{"@type":"Question","name":"How should a North-American utility specify the unit?","acceptedAnswer":{"@type":"Answer","text":"Provide its regulator specification, rated winding connection, insulation level, current, bypass scheme and controller/communications requirements. IEC/IEEE 60076-21 is a design reference; utility acceptance and the exact test schedule still need agreement."}}],"inLanguage":"en"}
```

```json
{"@context":"https://schema.org","@type":"BreadcrumbList","itemListElement":[{"@type":"ListItem","position":1,"name":"Products","item":"https://entogo.ca/products/"},{"@type":"ListItem","position":2,"name":"Voltage Regulation & Power Quality","item":"https://entogo.ca/products/families/voltage-regulation/"},{"@type":"ListItem","position":3,"name":"Step Voltage Regulator (SVR)"}],"inLanguage":"en"}
```

_Markdown twin of https://entogo.ca/products/step-voltage-regulator/ — generated at build time from the same content as the HTML page. Company facts, catalogue index and contact: https://entogo.ca/llms.txt_