In short: K-factor is calculated from the load’s harmonic spectrum, and the specification is the next UL rating at or above it. A 150 kVA, 480–208Y/120 V transformer feeding IT panels with 70 % third, 45 % fifth and 20 % seventh harmonic works out to K = 7.83, so K-9. A standard K-1 unit on that load is limited to 81.5 % of rated current under IEEE C57.110-2018, which is 339 A of its 416 A. Meanwhile triplen harmonics push 576 A through the neutral against 360 A per phase. Four numbers decide the purchase: K, the derating, the neutral current and the 200 % neutral bus. The transformer sizing calculator runs the rated currents, NEC 450.3(B) devices and fault current. This page adds the harmonic layer it assumes away, building on how to size a transformer and sizing transformer overcurrent protection.
What makes a load nonlinear, and why does it heat a transformer?
A linear load draws a sinusoidal current. Switch-mode power supplies in servers, variable-frequency drives, LED drivers and UPS rectifiers draw current in pulses. Those pulses are the 60 Hz fundamental plus harmonic currents at whole multiples: 180 Hz for the 3rd, 300 Hz for the 5th, 420 Hz for the 7th.
The RMS current alone does not show the damage. Winding eddy-current loss rises with the square of harmonic order, so 1 A at the 5th harmonic produces 25 times the eddy loss of 1 A at 60 Hz. A transformer can therefore overheat while the ammeter reads below nameplate. IEEE C57.110-2018 is the recommended practice for working out how much an existing dry-type or liquid-immersed transformer can carry when part of its load is nonsinusoidal. UL 1561, the dry-type standard for 600 V and below, is where the K-factor rating is defined; confirm with the manufacturer how K-factor is treated for medium-voltage units under UL 1562.
The h² scaling has a stated limit. A 2024 Scientific Reports analysis of C57.110 notes that the h² law holds for winding conductors smaller than 3 mm and is wrong for larger conductors above the 5th harmonic because of skin effect. Because skin effect slows the rise in loss, the method errs conservative for heavy bar windings.
How do you calculate K-factor?
UL 1561 defines the rating as a weighted sum over all harmonic orders h, with each current in per unit of rated RMS load current. To find the K-factor of a measured load, use the load’s own total RMS current as the per-unit base, so that Σ Ih(pu)² = 1:
K = Σ Ih(pu)² × h²
From a survey reading in percent of fundamental, normalize first. The same quantity then appears as IEEE C57.110’s harmonic loss factor:
K = F_HL = Σ (Ih ÷ I1)² × h² ÷ Σ (Ih ÷ I1)²
The two give the same number when both are computed on a total-RMS basis. A purely sinusoidal load gives K = 1. UL recognizes K-4, K-9, K-13, K-20, K-30, K-40 and K-50, and a standard general-purpose transformer is effectively K-1.
| Harmonic h | Ih ÷ I1 (survey) | (Ih ÷ I1)² | (Ih ÷ I1)² × h² |
|---|---|---|---|
| 1 | 1.00 | 1.0000 | 1.0000 |
| 3 | 0.70 | 0.4900 | 4.4100 |
| 5 | 0.45 | 0.2025 | 5.0625 |
| 7 | 0.20 | 0.0400 | 1.9600 |
| 9 | 0.08 | 0.0064 | 0.5184 |
| 11 | 0.06 | 0.0036 | 0.4356 |
| 13 | 0.04 | 0.0016 | 0.2704 |
| Sum | 1.7441 | 13.6569 |
These are the inputs of the worked example below, a spectrum typical of single-phase switch-mode IT load. The 3rd harmonic contributes the largest single term, but the 5th outweighs it once h² is applied.
Worked example: K-rating a 150 kVA transformer for an IT load
A 150 kVA, 480 V delta to 208Y/120 V dry-type transformer feeds server and workstation panels. A harmonic survey at the secondary reads 360 A RMS per phase with the spectrum in the table above.
I = kVA × 1000 ÷ (√3 × V)
IN = 3 × I1 × √[(I3 ÷ I1)² + (I9 ÷ I1)² + (I15 ÷ I1)² + …]
- Rated secondary current. I = kVA × 1000 ÷ (√3 × V) = 150 000 ÷ (208 × √3) = 150 000 ÷ 360.27 = 416.4 A. The load is 360 ÷ 416.4 = 86.5 % of rating, or 360 × 208 × √3 ÷ 1000 = 129.7 kVA.
- Normalize the spectrum. Σ (Ih ÷ I1)² = 1.7441, so RMS current = I1 × √1.7441 = 1.3206 × I1. Current total harmonic distortion is √(1.7441 − 1) = √0.7441 = 86.3 %.
- Weight by h². Σ (Ih ÷ I1)² × h² = 1 + 4.41 + 5.0625 + 1.96 + 0.5184 + 0.4356 + 0.2704 = 13.6569.
- Compute K. K = 13.6569 ÷ 1.7441 = 7.83.
- Pick the rating. The next UL rating at or above 7.83 is K-9. K-4 is undersized, and K-13 or K-20 buys margin the load does not need, unless the load is planned to grow.
- Check the neutral. Fundamental current I1 = 360 ÷ 1.3206 = 272.6 A. Triplens add arithmetically in the neutral, so IN = 3 × I1 × √(0.70² + 0.08²) = 3 × 272.6 × 0.7046 = 576.2 A. That is 576.2 ÷ 360 = 160 % of phase current and 576.2 ÷ 416.4 = 138 % of rated current.
- Check the neutral bus. A 200 % bus on a 416.4 A secondary is 2 × 416.36 = 832.7 A, which clears 576 A and leaves 31 % of the bus unused. A 100 % neutral rated at 416 A would be overloaded by 160 A.
Step 4 — K-factor from the survey spectrum
K = (1 + (3*a3)^2 + (5*a5)^2 + (7*a7)^2 + (9*a9)^2 + (11*a11)^2 + (13*a13)^2) / (1 + a3^2 + a5^2 + a7^2 + a9^2 + a11^2 + a13^2)
K = ratio
Step 6 — neutral current from the triplens
IN = 3 * I1 * sqrt(a3^2 + a9^2)
IN = A
The 160 % ratio checks against the physical ceiling. When single-phase current pulses on the three phases do not overlap, the neutral carries every pulse in turn, so IN² = 3 × Iphase² and IN ÷ Iphase = √3 = 1.732, or 173 %. A spectrum with this much 3rd harmonic sits close to that limit.
Second example: a drive panel with no triplens
A balanced panel of six-pulse drives reads 35 % at the 5th, 10 % at the 7th, 7 % at the 11th and 5 % at the 13th. Σ (Ih ÷ I1)² = 1 + 0.1225 + 0.01 + 0.0049 + 0.0025 = 1.1399. Σ (Ih ÷ I1)² × h² = 1 + 3.0625 + 0.49 + 0.5929 + 0.4225 = 5.5679. K = 5.5679 ÷ 1.1399 = 4.88, so K-9 again, not K-4. The neutral result is the opposite: with no triplens and balanced phases, the 5th, 7th, 11th and 13th cancel at the star point, and the neutral carries close to zero. The rule of thumb that drives mean K-4 fails here by 0.88. The drive panel needs the K-rating but not the double neutral, and the IT panel needs both.
How much must a standard transformer be derated?
For a transformer already installed, or a K-1 unit offered against a K-rated one, IEEE C57.110-2018 limits current so that winding load loss does not exceed its rated value. Rated load loss in per unit of I²R loss is P_LL-R = 1 + P_EC-R + P_OSL-R. Setting the other stray loss P_OSL-R aside and holding total winding loss at rated gives:
Imax(pu) = √[(1 + P_EC-R) ÷ (1 + F_HL × P_EC-R)]
P_EC-R is the rated eddy-current loss as a fraction of I²R loss. It should come from the manufacturer or from test data under the C57.110 procedure, never from another transformer’s datasheet. The Electrotek case study published on PQBlog assumes 8 % and gets 82 % capability at K = 7.56. The formula reproduces that: √(1.08 ÷ 1.6048) = 0.820.
Derated capability of a standard K-1 transformer
Imax = sqrt((1 + P) / (1 + K * P))
Imax = ratio
On the worked example: √(1.08 ÷ (1 + 7.83 × 0.08)) = √(1.08 ÷ 1.6264) = √0.6640 = 0.815. A standard 150 kVA unit can carry 0.815 × 416.4 = 339.3 A, which is 21 A short of the 360 A measured. To carry 360 A at 81.5 % capability, a standard unit needs 360 ÷ 0.815 = 441.7 A of rating, or 441.7 × 208 × √3 ÷ 1000 = 159.1 kVA. The next standard size is 225 kVA.
kVA needed = I × V × √3 ÷ (1000 × Imax)
Standard-transformer rating needed to carry the load
kVA = I * V * sqrt(3) / (1000 * Imax)
kVA = kVA
| K-factor of load | P_EC-R = 0.05 | P_EC-R = 0.08 | P_EC-R = 0.10 | P_EC-R = 0.15 |
|---|---|---|---|---|
| 1 (linear) | 100.0 % | 100.0 % | 100.0 % | 100.0 % |
| 4 | 93.5 % | 90.5 % | 88.6 % | 84.8 % |
| 7.83 (worked example) | 86.9 % | 81.5 % | 78.5 % | 72.7 % |
| 9 | 85.1 % | 79.2 % | 76.1 % | 70.0 % |
| 13 | 79.8 % | 72.8 % | 69.2 % | 62.4 % |
| 20 | 72.5 % | 64.5 % | 60.6 % | 53.6 % |
Each cell is √[(1 + P_EC-R) ÷ (1 + K × P_EC-R)]. The table shows why the input matters: the same K-13 load leaves anywhere from 62 % to 80 % of a standard unit usable, depending on a winding property only the manufacturer knows.
Which K-rating fits which load?
Where no survey exists, ABB’s 2023 technical paper gives a widely used starting guide. It is a starting point, not a code minimum. The K-13 commonly specified for general IT halls, as in AI data center power equipment, is a no-survey default with margin built in. A measured spectrum, like the worked example’s K = 7.83, can justify K-9, and the second example above shows a drive-heavy panel falling outside the guide in the other direction.
| Rating | Share of load generating harmonics | Typical application |
|---|---|---|
| K-1 | Little to none, typically under 15 % | General lighting, motors without drives |
| K-4 | Up to 35 % | Induction heating, SCR and AC drives |
| K-13 | 35 to 75 % | Schools, hospitals, electronically controlled lighting |
| K-20 | 60 to 100 % | Data processing, server loads, critical care |
| K-30 to K-50 | 100 %, known signature | Loads with a measured, consistently severe spectrum |
What do the NEC and the CEC require of the neutral?
Neither code requires a K-rating. Both codes regulate the neutral that triplens load, and both size the transformer’s overcurrent protection on rated current regardless of K.
| Requirement | NEC (NFPA 70, 2023) | CEC (CSA C22.1) |
|---|---|---|
| No neutral demand reduction for nonlinear load | 220.61(C)(2), nonlinear loads on a 4-wire, 3-phase wye | Rule 4-024(2)(a)(ii), non-linear loads on a 3-phase, 4-wire system |
| Neutral counted for ampacity adjustment | 310.15(E)(3), where the major portion of the load is nonlinear | No separate nonlinear clause cited here; apply the Section 4 ampacity rules |
| Secondary overcurrent device, dry-type 1000 V or less | Table 450.3(B), 125 %, next size up per Note 1 | Rule 26-254(2), 125 % secondary |
| Primary device with secondary protection | Table 450.3(B), 250 % | Rule 26-254(2), 300 % |
| Product standard for K-rated dry-type units | UL 1561 | CSA C22.2 No. 47 and CSA C9 |
For the 150 kVA example, 125 % × 416.36 = 520.4 A rounds up under Note 1 to a 600 A secondary device, the same with or without a K-rating. The 600 A conductor set still needs a neutral sized for 576 A of measured current, plus growth.
Where Canada differs. CEC Rule 4-024(2)(a)(ii) entered with the 2012 edition. It states that “there shall be no reduction in the size of the neutral for that portion of the load that consists of non-lineal [sic] loads supplied from a 3-phase, 4-wire system.” That matches the NEC prohibition in substance, but a Canadian design cites a different rule. For the Canadian market, dry-type transformer evaluation references CSA C22.2 No. 47 and CSA C9, which the ABB paper lists alongside UL 1561. The larger divergence is upstream. Under CEC Rule 26-254(2), a primary feeder may be set at 300 % of rated primary current where secondary protection is at 125 %, against the NEC’s 250 %. On a 600 V primary, the 144.3 A rated current gives a 433 A ceiling (400 A device) in Canada against 361 A (350 A device) under the NEC, as worked in sizing transformer overcurrent protection. Confirm the rule numbers against the edition the province has adopted.
What neutral bus rating does each transformer size need?
| kVA, three-phase | Secondary 208 V | 200 % neutral bus | Primary 480 V | Primary 600 V |
|---|---|---|---|---|
| 45 | 124.9 A | 249.8 A | 54.1 A | 43.3 A |
| 75 | 208.2 A | 416.4 A | 90.2 A | 72.2 A |
| 112.5 | 312.3 A | 624.5 A | 135.3 A | 108.3 A |
| 150 | 416.4 A | 832.7 A | 180.4 A | 144.3 A |
| 225 | 624.5 A | 1,249.1 A | 270.6 A | 216.5 A |
| 300 | 832.7 A | 1,665.4 A | 360.8 A | 288.7 A |
| 500 | 1,387.9 A | 2,775.7 A | 601.4 A | 481.1 A |
Every cell is kVA × 1000 ÷ (√3 × V), with the neutral column doubled. These are the rated currents the transformer sizing calculator produces before any harmonic adjustment.
What to specify
- The K-rating, as the next UL value at or above the K-factor calculated from a harmonic survey at the secondary, or from the load-type guide when no survey exists, under UL 1561 or CSA C22.2 No. 47.
- A 200 % neutral bus on any K-rated unit serving single-phase nonlinear load, with the neutral current computed from the triplen spectrum, not assumed. NEC 220.61(C)(2) and CEC Rule 4-024(2)(a)(ii) forbid reducing it.
- P_EC-R from the manufacturer’s test data, when a standard unit is being evaluated instead of a K-rated one, so the IEEE C57.110-2018 derating is computed on real winding data.
- Rated currents and overcurrent devices from the nameplate kVA under NEC Table 450.3(B) or CEC Rule 26-254, computed in the calculator.
- Temperature rise and insulation class, for example 220 °C insulation at 150 °C, 115 °C or 80 °C temperature rise. A lower rise gives thermal margin on top of the K-rating.
- Efficiency compliance. K-factor transformers are not among the types excluded from the 10 CFR 431.192 definition, and loss data is published under linear-load conditions. Evaluate no-load and load losses as for any other unit.
Common mistakes
- Normalizing to the fundamental and stopping there. Summing (Ih ÷ I1)² × h² without dividing by Σ (Ih ÷ I1)² gives 13.66 on the worked spectrum instead of 7.83. That points to K-20 where K-9 is correct. Check that Σ Ih(pu)² equals 1 before multiplying by h².
- Rounding K down to the nearest rating. The drive panel at K = 4.88 is not a K-4 load. The rating must be at or above the calculated value, so the answer is K-9.
- Sizing the neutral to phase current. On the IT panel, 360 A per phase puts 576 A in the neutral, 160 %. NEC 310.15(E)(3) counts that neutral as current-carrying, and NEC 220.61(C)(2) and CEC Rule 4-024(2)(a)(ii) forbid reducing it.
- Treating the K-rating as a harmonic filter. A K-9 unit survives the heat but passes 86.3 % current distortion upstream untouched. Compliance at the utility connection is a separate calculation under IEEE 519, covered in harmonic distortion and IEEE 519 limits.
- Borrowing a P_EC-R figure. At K = 13, moving P_EC-R from 0.05 to 0.15 changes a standard unit’s capability from 79.8 % to 62.4 %. A borrowed percentage is not design data.
Where Entogo fits
Entogo’s three-phase dry-type distribution transformer covers 15 to 2500 kVA, from the 600 V class (480 V to 208Y/120 V) to the 35 kV class. It uses 220 °C insulation with 150 °C rise standard and 115 °C or 80 °C optional, and K-factor windings for nonlinear load are an option. It is designed and built to UL 1561 / UL 1562, NEMA ST 20, CSA C9 and DOE 10 CFR 431; UL (cULus)/CSA certifiable on request. Where a continuously energized load is served from a medium-voltage primary (15, 25 or 35 kV class) and low no-load loss justifies the cost, the amorphous-core dry-type transformer addresses a different problem, core loss, and is evaluated as in total owning cost of a transformer. Its catalog entry does not list a K-factor option, so the harmonic spectrum belongs in the quote request.
Entogo builds the transformer and the distribution switchboard or panelboard it feeds in its own factory; the panelboard is designed and built to UL 67 / UL 891; UL (cULus)/CSA certifiable on request. Quoting both together lets the 200 % neutral bus, the secondary conductors under NEC 240.21(C) and the panel neutral be checked against the same harmonic survey for data center and industrial projects. Run the rated currents in the transformer sizing calculator, then send the harmonic survey with a transformer quote request, or browse transformers and substations.
A K-rating is a calculation, not a category. Normalize the survey spectrum, weight it by h², and take the next UL rating at or above the result. Then compute the triplen neutral current and give it a 200 % bus. Where a standard unit is offered instead, derate it with IEEE C57.110 using the manufacturer’s own eddy-loss figure. The 150 kVA example shows the stakes: K-9 at 150 kVA against 225 kVA of standard transformer, and a neutral carrying 160 % of phase current that neither the NEC nor the CEC allows to be reduced.