Power Equipment

Pad-mounted transformer sizes: 75 to 2500 kVA

Entogo builds three-phase pad-mounted distribution transformers in every standard rating from 75 to 2500 kVA: liquid-filled, dead-front units for 12.47 / 13.2 / 13.8 kV (15 kV class), 24.94 kV (25 kV class) and 34.5 kV (35 kV class) primaries stepping down to 208Y/120, 480Y/277 or 600Y/347 V at 60 Hz, designed and built to IEEE C57.12.34 / C57.12.28 and DOE 10 CFR 431 in Entogo's own factory. Engineered-to-order units ship in 16–24 weeks; UL (cULus) / CSA certification is available on request within a guaranteed 36-week worst case. Pick a rating below for its full-load and fault currents.

Full-load current by rating

Three-phase line current at rated load: amperes = kVA × 1000 ÷ (√3 × V). Primary currents assume the nominal system voltage; secondary currents are at the secondary line-to-line voltage.

Full-load current of three-phase pad-mounted transformers by kVA rating
Rating 208Y/120 V secondary 480Y/277 V secondary 600Y/347 V secondary 12.47 kV primary 13.8 kV primary 24.94 kV primary 34.5 kV primary
75 kVA 208 A90.2 A72.2 A 3.5 A3.1 A1.7 A1.3 A
112.5 kVA 312 A135 A108 A 5.2 A4.7 A2.6 A1.9 A
150 kVA 416 A180 A144 A 6.9 A6.3 A3.5 A2.5 A
225 kVA 625 A271 A217 A 10.4 A9.4 A5.2 A3.8 A
300 kVA 833 A361 A289 A 13.9 A12.6 A6.9 A5.0 A
500 kVA 1,388 A601 A481 A 23.1 A20.9 A11.6 A8.4 A
750 kVA 2,082 A902 A722 A 34.7 A31.4 A17.4 A12.6 A
1000 kVA 2,776 A1,203 A962 A 46.3 A41.8 A23.1 A16.7 A
1500 kVA 4,164 A1,804 A1,443 A 69.4 A62.8 A34.7 A25.1 A
2000 kVA 5,551 A2,406 A1,925 A 92.6 A83.7 A46.3 A33.5 A
2500 kVA 6,939 A3,007 A2,406 A 116 A105 A57.9 A41.8 A

Every rating links to its own page with fault-current tables, ratings at a glance and typical applications. The catalogue page for the product family is the Three-Phase Pad-Mounted Distribution Transformer.

Construction common to every rating

What is fixed across the range, and what is specified per project.

  • Designed and built to IEEE C57.12.34 (three-phase pad-mounted) and C57.12.28 (enclosure integrity), tested per C57.12.90, CSA C88; 60 Hz.
  • Primary 12.47 / 13.2 / 13.8 kV (15 kV class, 95 kV BIL), 24.94 kV (25 kV class, 125 kV BIL) or 34.5 kV (35 kV class, 150 kV BIL); secondary 208Y/120, 480Y/277, 240/120 or 600 V.
  • Liquid-filled, ONAN, 65 °C average winding rise; mineral oil standard, FR3 natural ester optional; copper or aluminium windings.
  • Dead-front, 200 A loadbreak bushing wells; loop-feed (6 bushings) or radial-feed (3 bushings); live-front on request.
  • De-energized tap changer, ±2 × 2.5 % standard.
  • Core-and-coil designed to DOE 10 CFR 431 minimum efficiency; amorphous-metal core optional for loss-evaluated bids.
  • Tamper-resistant NEMA 3R cabinet, ANSI 70 green powder coat, pad-lockable.
  • UL (cULus) / CSA certification available on request; minimum 36-month manufacturer warranty, extended terms on major power equipment per contract.

FAQ

Common questions

What sizes do three-phase pad-mounted transformers come in?
The standard three-phase ladder is 75, 112.5, 150, 225, 300, 500, 750, 1000, 1500, 2000 and 2500 kVA (IEEE C57.12.00), and Entogo builds pad-mounted units in every one of those ratings, with 3000 kVA available on request.
How do I calculate the full-load current of a pad-mounted transformer?
Full-load current in amperes = kVA × 1000 ÷ (√3 × line-to-line volts). A 500 kVA unit delivers about 601 A at 480 V, 1,388 A at 208 V and 481 A at 600 V; on a 12.47 kV primary it draws about 23 A. The table on this page lists every rating.
Which primary and secondary voltages are available?
Primaries: 12.47, 13.2 and 13.8 kV (15 kV class, 95 kV BIL), 24.94 kV (25 kV class, 125 kV BIL) and 34.5 kV (35 kV class, 150 kV BIL). Secondaries: 208Y/120, 480Y/277, 240/120 and 600 V. Every unit is 60 Hz; other combinations are built to order.
How long does an Entogo pad-mounted transformer take to deliver?
Pad-mounted transformers are engineered to order and ship from Entogo's own factory in 16–24 weeks. When the order needs new UL (cULus) or CSA certification, delivery is guaranteed within 36 weeks — against the one-to-four-year lead times common in the merchant market.

Configure & quote

Specify the rating and voltages and get a project-based quote.