Entogo
Distribution Transformers
Choose by phase, installation and network connection.
Start with the utility connection and installation: a single-phase pad-mounted unit, a three-phase transformer and a complete pole-mounted package serve different layouts. Include service voltage, secondary voltage, kVA, phase arrangement, protection and the utility specification in the inquiry.
Distribution Transformers
Single-Phase Pad-Mounted Transformer
Entogo supplies single-phase pad-mounted transformers for underground distribution. Specify the utility voltage, kVA, dead-front cable interface, loop or radial feed and secondary service before selecting the configuration.
View
Distribution Transformers
Three-Phase Pad-Mounted Distribution Transformer
Three-phase pad-mounted distribution transformer for North American utility, commercial and industrial service — 75–2500 kVA, 12.47–34.5 kV class primary to 480Y/277 or 208Y/120 secondary, dead-front loop/radial-feed, NEMA 3R. Designed to IEEE C57.12.34 and DOE 10 CFR 431; UL/CSA certifiable.
View
Distribution Transformers
Single-Phase Overhead (Pole-Mounted) Distribution Transformer
Single-phase overhead pole-mounted distribution transformers for North American utility lines — 10 to 167 kVA, 7200 / 12470GrdY / 24940GrdY primary to 120/240 V secondary, conventional or completely self-protected (CSP). Designed to IEEE C57.12.20 and DOE 10 CFR 431 efficiency, 60 Hz; UL / CSA certifiable.
View
Distribution Transformers
Combined Pad-Mounted Transformer (Integrated MV Switching)
Combined pad-mounted transformer integrating the medium-voltage load-break switch, fuse protection and low-voltage distribution with the transformer in one tamper-resistant tank — 75–2500 kVA, 15/25/35 kV class, 60 Hz. Designed to IEEE C57.12.34/.28; UL/CSA certifiable.
View
Distribution Transformers
Overhead Distribution Transformer Set (Pole-Mount Package)
A complete overhead pole-mount distribution package — transformer, fused cutout, lightning arrester, secondary/metering pedestal, jumpers and hardware — engineered to a single 15 kV class, 60 Hz specification. Transformer designed to IEEE C57.12.20 and DOE 10 CFR 431; UL/CSA certifiable.
View
Design references
Power & Distribution
How to size a transformer: a practical guide to kVA selection
How to convert a real electrical load into the right transformer kVA: the calculation, the standard ANSI/IEEE rating ladder, and the margins for continuous duty, future growth, ambient and altitude that sit between calculated load and nameplate.
View
Power & Distribution
De-energized taps or a load tap changer? Specifying transformer voltage regulation
Transformer regulation is %R cos θ + %X sin θ plus a small quadratic term. A 1500 kVA, 5.75 %Z unit at 0.85 PF drops 3.85 %, so a 13.3 to 14.0 kV primary needs the 13 455 V tap to hold 456 to 504 V. The full ANSI C84.1 Range A primary swing needs an OLTC or a step regulator.
View
Standards & Compliance
How do transformers get approved for use in Canada?
Before a transformer can be energised in Canada, the Canadian Electrical Code requires it to be "approved" — either certified by an SCC-accredited body (a CSA, cULus or cCSAus mark) or field-evaluated to CSA SPE-1000. A US-only "UL Listed" mark is not enough. Here is how the approval system actually works.
View
For Canadian and US projects, include the utility specification, service frequency and required approvals. State whether the order is for the transformer alone or an integrated equipment package.
Discuss your equipment requirements