Planning tool
Transformer Sizing & Overcurrent Protection Calculator
Size a transformer and its protection in one place — full-load current, kVA selection, primary and secondary overcurrent protection per NEC 450.3(B) or CEC Section 26, the available secondary fault current for downstream AIC / SCCR, and a NEMA enclosure suggestion. For the US (NEC) and Canada (CEC).
Size your transformer
Describe the transformer and get sizing, protection & fault current.
Enter a kVA rating or a load to size it. Every result is shown on this page — no sign-up required.
Transformer
Rating
Primary full-load current
Secondary full-load current
Overcurrent protection
Maximum ratings per the table — a lower standard device may be selected. The 125% rows permit the next higher standard size (NEC 450.3(B) Note 1); the others are ceilings.
Applicable references
Section numbering varies by adopted edition — verify with your AHJ / ESA.
Check these
Assumptions & notes
Next steps
- — Confirm the nameplate %impedance and vector group from the datasheet
- — Size secondary conductors & protection (NEC 240.21(C) / CEC Section 4) — a separate step
- — Verify downstream panel / switchgear AIC & SCCR against the available fault current
- — Confirm taps, temperature rise, K-factor and enclosure for the application
Estimate only. These numbers are a quick planning estimate from your inputs and standard assumptions — handy for scoping and feasibility, not a permit or construction document. Real protection, conductor and fault-current design depends on your site, the code edition your area has adopted and the equipment ratings, so confirm with a registered engineer (PE / P.Eng) and your AHJ / ESA before ordering equipment or building.
Good to know
Transformer sizing, protection & fault current
Common questions about full-load current, NEC 450.3(B) / CEC Section 26 overcurrent protection, available fault current and enclosure selection — for the US (NEC) and Canada (CEC).
- What size transformer do I need for a given load?
- Enter the load in kVA, amps or kW (with power factor) and the calculator divides it by a design loading factor (0.80 by default) and rounds up to the next standard kVA. As a rough guide, a 220 kVA load points to a 300 kVA transformer; a 90 kVA load points to a 112.5 kVA transformer. It also returns the primary and secondary full-load current so you can size the upstream and downstream gear. Confirm the final rating, taps and temperature rise for your application.
- How do you calculate transformer full-load current (kVA to amps)?
- For a three-phase transformer, full-load current I = kVA × 1000 ÷ (V × √3); for single-phase, I = kVA × 1000 ÷ V. For example, a 300 kVA three-phase transformer with a 208 V secondary draws about 833 A on the secondary, and about 289 A on a 600 V primary. The calculator returns both winding currents from the kVA and the two voltages.
- How is transformer overcurrent protection sized under NEC 450.3(B)?
- For transformers 1000 V and less, NEC Table 450.3(B) sets the maximum overcurrent device as a percentage of the winding’s rated current. With primary protection only: 125% where the primary current is 9 A or more (the next standard size up is permitted by Note 1), 167% for 2–9 A, and 300% below 2 A. With both primary and secondary protection: up to 250% on the primary and 125% on the secondary (167% below 9 A). The calculator applies the table to the full-load current and selects the standard device from NEC 240.6(A).
- What fuse or breaker size do I need for a 300 kVA transformer?
- Take the winding full-load current and apply the NEC 450.3(B) percentage. A 300 kVA, 600 V three-phase primary draws about 289 A; with primary-only protection at 125% that is about 361 A, so the next standard device is 400 A (Note 1). The exact device depends on inrush, coordination and whether the secondary is separately protected — the calculator shows the maximum and the recommended standard size for both windings.
- How do I find the available fault current at a transformer secondary?
- The infinite-source estimate is the secondary full-load current divided by the per-unit impedance: I_sc = secondary FLA ÷ (%Z ÷ 100). For a 300 kVA, 208 V secondary (≈833 A) at 5% impedance, that is roughly 16.7 kA. Enter the nameplate %impedance and the calculator returns the available fault current and the next standard interrupting rating, so you can confirm the AIC of downstream breakers and the SCCR of panelboards and switchgear. A finite utility source lowers it and motor contribution raises it — confirm with a full short-circuit study.
- Does the calculator work for Canada (CEC Section 26)?
- Yes. Switch the code reference to CEC 2024 and the protection percentages follow CSA C22.1 Section 26 instead of the NEC. For dry-type transformers 750 V and under, Rule 26-254(1) caps the primary device at 125% of rated primary current; Rule 26-254(2) allows the primary feeder to go up to 300% when a secondary device is set at no more than 125% — versus the NEC ceiling of 250% on the primary. Liquid-filled and over-750 V units fall under 26-250 / 26-252, so confirm those against CSA C22.1 and your AHJ / ESA. This makes it one of the few transformer sizing tools that covers both NEC and CEC.
- Is this a code-compliant calculation I can submit for permit?
- No — it is a free estimate for early planning, not a permit or construction document. Overcurrent percentages, conductor ampacity, secondary-conductor protection (NEC 240.21(C)), grounding and a full short-circuit study are separate design steps. Use it to scope and sanity-check, then confirm the numbers with a registered engineer (PE / P.Eng) and your AHJ / ESA.
The method behind the numbers
These guides explain what the calculator computes and why — useful for a submittal, a spec or learning the rules.
- Guide Sizing transformer overcurrent protection (NEC 450.3(B) & CEC 26) Primary and secondary OCPD, the US-vs-Canada difference, and available fault current for downstream AIC / SCCR — with worked examples. Read the guide
- Guide How to size a transformer: a practical guide to kVA selection From a real load to the right standard kVA — the calculation, the rating ladder and the margins for continuous duty, growth, ambient and harmonics. Read the guide