kVA rating (apparent power)
Also: MVA
A transformer is rated in kilovolt-amperes (kVA) or megavolt-amperes (MVA): rated voltage multiplied by rated current, independent of the load power factor. To size a unit, divide the connected or calculated load by the intended loading (often 80 %) and round up to the next standard rating on the ANSI/IEEE C57.12.00 ladder — 75, 112.5, 150, 225, 300, 500, 750, 1000, 1500, 2000 and 2500 kVA for three-phase distribution units.
Related: How to size a transformer (kVA selection) · Transformer configurator & quote
Pad-mounted transformer
Also: pad-mount, padmount
A liquid-filled distribution transformer in a tamper-resistant, dead-front steel cabinet that sits on a concrete pad at ground level and is fed by underground primary cable. Three-phase units follow IEEE C57.12.34 (single-phase: C57.12.38) with enclosure integrity per ANSI C57.12.28. Typical North-American ratings: 15 / 25 / 35 kV class primary, 208Y/120 V or 480Y/277 V secondary, 75–2500 kVA — the range Entogo builds to DOE 10 CFR 431 efficiency.
Related: Three-Phase Pad-Mounted Distribution Transformer · Combined Pad-Mounted Transformer
Pole-mounted (overhead) transformer
Also: overhead distribution transformer, CSP transformer
A distribution transformer hung on a utility pole and fed from overhead lines through high-voltage bushings, protected by fuse cutouts and surge arresters — or, in a CSP (completely self-protected) unit, by an internal secondary breaker, primary fuse and arrester. Built to IEEE C57.12.20; single-phase units run from about 10 to 167 kVA and are the standard way North-American utilities serve rural and suburban secondary networks.
Related: Single-Phase Overhead (Pole-Mounted) Distribution Transformer · Overhead Distribution Transformer Set (Pole-Mount Package)
Dry-type transformer
Also: ventilated dry-type, cast-resin transformer
A transformer whose windings are cooled and insulated by air (ventilated, encapsulated or cast-resin) instead of a liquid, so it can be installed indoors close to the load without oil containment or fire separation. Low-voltage units are built to UL 1561 / CSA C22.2 No. 47 and medium-voltage units to UL 1562, with DOE 10 CFR 431 efficiency levels; insulation systems are typically 220 °C class with 80, 115 or 150 °C temperature rise.
Related: Three-Phase Dry-Type Distribution Transformer · Amorphous-Core Dry-Type Transformer · Dry-type vs. liquid-filled transformers
Liquid-filled (oil-immersed) transformer
Also: oil-filled transformer, ester-filled transformer
A transformer whose core and windings are immersed in mineral oil or a less-flammable natural-ester fluid that both insulates and carries heat to the tank and radiators. Liquid units tolerate overload better and are more efficient per kVA than dry-type, which is why pad-mounted, substation and power transformers are almost always liquid-filled (IEEE C57.12.00 / C57.12.90). Indoor installations need the vault or containment rules of NEC Article 450 or CEC Section 26.
Related: 36 kV Oil-Immersed Power Transformer · Dry-type vs. liquid-filled transformers
Amorphous-core transformer
Also: amorphous metal transformer, AMDT
A distribution transformer whose core is wound from amorphous (non-crystalline) iron-based ribbon instead of grain-oriented silicon steel. The random atomic structure cuts no-load (core) loss by roughly 60–70 %, which matters because core loss is paid 24 hours a day regardless of load. The trade-off is a somewhat larger, heavier core. Entogo offers amorphous-core dry-type units for owners who buy on lifetime energy cost rather than first cost.
Related: Amorphous-Core Dry-Type Transformer (High-Efficiency) · Grain-oriented electrical steel supply chain
Wound-core (3-D triangular core) transformer
Also: three-dimensional wound core
A transformer whose core is wound from continuous steel strip rather than stacked from cut laminations. In a three-dimensional triangular wound core the three limbs sit at 120°, so every phase sees an identical, joint-free magnetic path: lower no-load loss, lower magnetising current and inrush, and less audible noise than a conventional stacked core. Entogo supplies this construction in oil-filled or dry-type distribution ratings.
Related: Three-Dimensional Wound-Core Transformer (Low-Loss)
Basic impulse insulation level (BIL)
Also: basic lightning impulse insulation level
The peak of the standard 1.2/50 µs lightning-impulse voltage wave that a transformer or switchgear insulation system is designed to withstand. BIL is tied to voltage class in ANSI/IEEE C57.12.00 and C37.20.2: typically 95 kV for 15 kV class, 125 kV for 25–27 kV class and 150 kV for 34.5–38 kV class. Specify the BIL the utility or the interconnection study requires — it drives clearances, bushings and the arrester rating.
Voltage class (15 kV / 25 kV / 35 kV)
The North-American way of grouping medium-voltage systems by insulation level rather than exact operating voltage. 15 kV class covers 12.47 kV and 13.8 kV systems, 25 kV class covers 24.94 kV, and 35 kV class covers 34.5 kV; switchgear expresses the same tiers as rated maximum voltages of 15, 27 and 38 kV (ANSI/IEEE C37.20.2). A transformer or switchgear is specified by class first, then by the actual system voltage and BIL.
Related: Metal-Clad Switchgear (Drawout MV) · Choosing a facility distribution voltage
Percent impedance (%Z)
Also: transformer impedance
The transformer’s internal impedance expressed as the percentage of rated primary voltage needed to circulate rated current with the secondary short-circuited. It sets the secondary fault current (approximately rated current ÷ %Z, so a 5.75 % unit can deliver about 17 times rated current into a bolted fault) and the voltage regulation under load. Utilities and engineers specify it to keep downstream switchgear ratings and voltage drop within limits.
Related: How to size a transformer (kVA selection) · Transformer impedance (%Z) selection
Temperature rise (55 / 65 / 80 / 115 / 150 °C)
The average winding temperature rise above a 30 °C average ambient at rated load. Liquid-filled units are rated 55 °C or 65 °C rise; dry-type units 80, 115 or 150 °C rise on a 220 °C insulation system. A lower rise means more copper or aluminium and a lower-loss, longer-life design with built-in overload margin — a 65 °C liquid unit, for example, can carry a 55 °C rated load with about 12 % extra capacity.
DOE 10 CFR 431 efficiency (DOE 2016 / 2029)
Also: DOE efficiency, NRCan efficiency
The U.S. Department of Energy minimum efficiency levels for distribution transformers (liquid-filled, low-voltage dry-type and medium-voltage dry-type), measured at a reference load — 50 % of rating for liquid and MV dry-type, 35 % for LV dry-type. The 2016 levels apply to units made since 1 January 2016; the April 2024 final rule raises them for units manufactured from 2029. Canada enforces equivalent levels through NRCan’s Energy Efficiency Regulations (CSA C802 series). Entogo designs its North-American transformers to the DOE levels.
Related: Three-Phase Pad-Mounted Distribution Transformer · Transformer efficiency standards — DOE 10 CFR 431 · Total owning cost and transformer loss evaluation
Loop-feed vs. radial-feed
The two primary-cable arrangements of a pad-mounted transformer. A radial-feed unit has one set of primary bushings and is the dead end of a feeder. A loop-feed unit has two sets of bushings and loop (sectionalizing) switches, so the underground loop passes through the transformer and any one unit can be isolated for maintenance while the rest of the loop stays energised from the other direction — the standard choice for utility and campus networks.
Dead-front vs. live-front
Dead-front equipment keeps every energised part behind insulated, separable elbow connectors (IEEE 386) so no live metal is exposed when the cabinet is opened; live-front equipment uses exposed porcelain bushings. Dead-front construction is the North-American norm for pad-mounted transformers, sectionalizing cabinets and pad-mounted switchgear because it allows loadbreak switching and elbow-to-bushing testing with hot sticks at a safer working distance.
Related: Pad-Mounted Sectionalizing / Junction Cabinet
Unit substation (compact secondary substation)
Also: packaged substation, CSS, unitized substation
A factory-assembled package that close-couples an incoming medium-voltage section (load-interrupter switch and fuses or a breaker), a transformer and a low-voltage switchgear or switchboard section through solid bus, built to IEEE C37.121. Because the whole assembly is wired and tested in the factory, a unit substation shortens site work from weeks to days — the format Entogo uses for its pad-mounted compact secondary and 36 kV outdoor unit substations.
Related: Pad-Mounted Compact Secondary Unit Substation · Prefabricated vs. conventional substations · Medium-voltage service and primary metering
Step-up (collector) transformer
Also: inverter-duty transformer, GSU
In a solar, wind or battery plant, the transformer that raises inverter output (typically 480–800 V) to the collection-system voltage, most often 34.5 kV, before the plant’s main step-up to transmission. Inverter-duty units are designed to IEEE C57.159 for harmonic content, cyclic loading and the DC offset inverters can impose. Entogo packages them on skids with the medium-voltage switchgear as a solar / storage unit substation.
Related: Solar / Storage Skid — Inverter-Duty Step-Up Unit Substation · Modular Skid-Mounted Unit Substation · IEEE 1547 DER grid interconnection
K-factor
A rating (K-4, K-13, K-20 …) that states how much harmonic current a dry-type transformer can carry without exceeding its temperature limit, calculated by the UL 1561 method from the harmonic spectrum of the load. Non-linear loads such as UPS systems, variable-frequency drives and switch-mode power supplies raise eddy-current loss in the windings; a K-13 rating is a common specification for data-centre and industrial-drive transformers.
Related: Power equipment for AI data centres · Do you need a K-rated transformer?
Taps (de-energized tap changer)
Also: DETC, tap changer
Extra connections on the high-voltage winding that change the turns ratio in small steps so a transformer can deliver nominal secondary voltage when the supply runs persistently high or low. The North-American standard is four 2.5 % taps — two above and two below nominal (±5 %) — selected with the transformer de-energised. On-load tap changers (OLTC) that switch under load are reserved for large power transformers.
Related: Transformer voltage regulation and tap changers